  Connection to contact output type controller: 

 

 

When connected to ON/OFF signal, output is produced upon shorting the C1-C2 terminals. 

 

 

8-2. Connection of More Than One Unit to Controller

 

In case the controller is of the current input type, control input signals should be wired in series. 
When the allowable range of load resistance of the 4-20mA output controller is 600Ω, maximum of six units can be connected. 

Since PAC27 units have control circuits of different electric potentials, auto and manual have to be switched individually. 

 

 

 

 

9. Alarm Function (standard equipment)

 

9-1. Overcurrent Protection Alarm

 

This alarm is put into action when the value of current detected by the regulator (built-in CT) exceeds approx. 130% of the rated current, blocks 
gate signals of thyristors and stops output, at which time current flows across the alarm output terminals AL1 and AL2. The monitor lamp [O.C.] 

lights. When the overcurrent protection alarm is activated, turn the power off and apply it again to reset the alarm. 
Power should be turned on again after removing the cause of overcurrent. 

 

9-2. Thyristor Overheating Alarm

 

This alarm is put into action when thyristor elements are heated to exceed its rated temperature, blocks the gate signal of the thyristor and stops 

output, at which time current flows across the alarm output terminals AL1 and AL2. The monitor lamp [O.H.] lights. 
The normal state is restored automatically when the thyristor temperature falls due to absence of output. 

When this function is in action, use the instrument in improved radiating conditions or with reduced load current. 

 

9-3. Thyristor Trouble Alarm

 

The trouble modes of thyristor element are mostly short-circuits. 
This function is in action when there is output voltage without control-input signal or when it is extremely slight if any, and current flows across 

the alarm output terminals AL1 and AL2. The monitor lamp [THY] lights. 

When the load is open, a high voltage is generated on the output side and this alarm is activated. Do not energize the instrument while the load 
is open. If the thyristor trouble lamp lights despite a load being connected, repair will be required. 

Please call our local business office or service center nearest you. 
 

The AL1 and AL2 are common output terminals for the 4 alarms. 
1. Monitor lamp [O.C.] lights: The action of the overcurrent protection circuit - Standard 

2. Monitor lamp [O.H.] lights: The action of the SCR overheating alarm - Standard 
3. Monitor lamp [THY] lights: The action of the SCR trouble alarm - Standard 

4. Monitor lamp [FUSE] lights: Rapid fuse break - Optional 

 
 
 

 

In the case of PAC27P2 -

 

Summary of Contents for PAC27

Page 1: ...to get into the product If something gets in by mistake and it is necessary to insert your hand or tool inside it make sure to turn the power off and to confirm that the condition are safe enough to...

Page 2: ...2YHUKHDWLQJ ODUP 7K ULVWRU 7URXEOH ODUP 3RZHU GMXVWPHQW DQG 6RIW 6WDUW 7LPH GMXVWPHQW QWHUQDO 3RZHU 5HJXODWLRQ 6RIW 6WDUW 7LPH GMXVWPHQW 9DULRXV KDUDFWHULVWLFV XUUHQW DSDFLW DQG DORULILF 9DOXH PELHQW...

Page 3: ...3 1 Confirmation of Specification Codes Please double check that the delivered product is exactly as you specified If you need further information please get in touch with our nearest local office...

Page 4: ...er adjuster SOFT START Soft start time adjuster HEATER SET Heater setting device for heater break alarm option H B SET Heater break alarm setting device option Terminal marking and description C1 C2 C...

Page 5: ...perature which exceeds 40 C Temperature allowed for this instrument is below 50 C 2 Humidity which exceeds 90 RH 3 Flammable gas corrosive gas or gas or particles that can deteriorate electrical insul...

Page 6: ...as to keep it from easy contact with persons It has to be installed vertically for heat radiation leaving more than 100 mm spaces above and below it respectively If it is inevitable to install the in...

Page 7: ...7 6 Circuit Block Diagram and Terminal Marking Terminal Marking Control Terminal No 1 18 See Page 4 2 2 Power Load Circuits...

Page 8: ...ity When T terminals are wired use wire material of 0 5 mm2 minimum 8 Wiring for Control Signals For control signals M3 5 terminal screws are used Use a crimp style terminal of more than 3 5 mm in ins...

Page 9: ...d temperature blocks the gate signal of the thyristor and stops output at which time current flows across the alarm output terminals AL1 and AL2 The monitor lamp O H lights The normal state is restore...

Page 10: ...fect of suppressing the rush current of a heater Setting is possible from less than one second min to more than 30 seconds max The longer the set time the slower the response of output Time should be...

Page 11: ...In case ambient temperature exceeds 50 C the instrument should be used with load current as illustrated below 11 3 Control System and Output Waveform 11 4 Special Heater and Feedback Control Type of h...

Page 12: ...dealing with low voltage command When power line is wired as a precaution against accidental short circuit make sure to install one molded case circuit breaker for each PAC27 The current capacity of...

Page 13: ...h a thyristor In case an ordinary transformer is used no problem will be caused when the load rate is held below 70 of the rating for the transformer 13 2 When Electromagnetic Switch Contactor Is Used...

Page 14: ...operation manual power adjuster switch is used voltage current input type 14 1 4 External power Base residual power adjuster 14 1 5 Contact input High low power adjuster When an external power adjust...

Page 15: ...ssumption that voltage and current have similar waveforms Depending on the types of loads however voltage has a waveform which is different from or out of proportion to that of current If this is the...

Page 16: ...sed for almost all types of heaters and allows for precision control of temperature As the constant power control is meant for a heater load a correct power level is unable to be attained for other lo...

Page 17: ...imiting works at 0 of the rated current and no output is produced If the instrument is used without the current limit setting device the control terminals CL2 and CL3 have to be short circuited Then t...

Page 18: ...m with no condensation Storage temperature between 20 and 65 C Applicable standards Safety IEC 60947 4 EN60947 4 EMC EN60947 4 EMC immunity EN60947 4 on condition that designated noise filter is used...

Page 19: ...ne load circuit This sometimes happens during trial run 3 Base power or low power regulator is connected It is for preventing minimum value of output from being 0 Detach low power regulator and rechec...

Page 20: ...Specialists Head Office 2 30 10 Kitamachi Nerima ku Tokyo 179 0081 Japan Phone 81 3 3931 7891 Fax 81 3 3931 3089 E MAIL exp dept shimaden co jp URL http www shimaden co jp The contents of this manual...

Reviews: