Shield T3 60 – 500KVA User Manual
51
Submenu Name
Contents
Meaning
RS232 Protocol
Selection
SNT Protocol, Modbus Protocol, YD/T
Protocol and Dwin
(
For factory use
)
Baud rate
Setting the baud rate of SNT, Modbus
and YD/T
Modbus Mode
Setting mode for Modbus: ASCII and
RTU selectable
Modbus parity
Setting the parity for Modbus
USER
Output voltage
Adjustment
Setting the Output Voltage
Bypass Voltage Up
Limited
Up limited working Voltage for
Bypass
,
se10%
,
+15%
,
+20%
,
+25%
Bypass Voltage Down
Limited
Down limited working Voltage for
Bypass
,
settable:-10%
,
-15%
,
-20%
,
-30%
,
-
40%
Bypass Frequency
Limited
Permitted working Frequency for
Bypass
Settable
:
+-1Hz
,
+-3Hz
,
+-5Hz
Dust Filter Maintenance
Period
Setting Dust Filter Maintenance Period
BATTERY
Battery Number
Setting the number of the battery
(
12V
)
Battery Capacity
Setting of the AH of the battery
Float Charge
Voltage/Cell
Setting the floating Voltage for
battery cell
(
2V
)
Boost Charge
Voltage/Cell
Setting the boost Voltage for battery
cell
(
2V
)
EOD(End of discharge)
Voltage/Cell,@0.6C
Current
EOD voltage for cell battery,@0.6C
current
EOD(End of charge)
Voltage/Cell,@0.15C
Current
EOD voltage for cell battery,@0.15C
current
Charge Current Percent
Limit
Charge current (percentage of the
rated current)
Battery Temperature
Compensate
Coefficient for battery temperature
compensation
Boost Charge Time Limit Setting boost charging time
Auto Boost Period
Setting the auto boost period
Auto Maintenance
Discharge Period
Setting the period for auto
maintenance discharge
SERVICE
System Mode
Setting the system mode: Single ,
parallel, Single ECO, parallel ECO, LBS,
parallel LBS