Section
5
Sealed System
5
-2
ÉßÎÒ×ÒÙ
R-410A is incompatible with R-22 refrigerant. R-410A is used at much higher operating pressures than
R-22 and other newer refrigerants.
Vapor pressures are typically as follows: 215.3 psi @ 70° F low side and 490.2 psi @ 130° F high side.
R-410A designed systems employ thicker walled tubing, and compressors capable of withstanding the
higher pressures of R-410A. R-410A systems require different installation and service procedures.
R-410A should only be used in equipment specifically designed and constructed for higher pressure
refrigerants.
R-410A needs service personnel to understand why all refrigerant flow controls, valves and driers have
changed and must be properly applied with newly designed and built compressors.
Filter-driers used with R-22 refrigerants are not compatible with an R-410A sealed system. When
installing or replacing a filter-drier in an R-410A system, make sure the replacement filter-drier is
specifically designed for R-410A refrigerant systems.
×ÓÐÑÎÌßÒÌ
New equipment that uses R-410A will require service personnel to acquire different tools and equipment, safety
standards and fundamentals when repairing systems in the field.
R-410A operates at considerably higher pressures and requires the use of special tanks, gauges and recovery
equipment.
Servicers will need to have dedicated equipment as listed:
R-410A - Manifold
Servicers will need to have accommodating equipment as listed:
R-410A - Recovery equipment
R-410A - Leak Detector
ÒÑÌÛ
For further information concerning section 608 of the Clean Air Act, or any other issue related to stratospheric ozone
protection, please call the Stratospheric Ozone Information Hotline at (800) 296-1996.
Phase-out schedule in the U.S.
http://www.epa.gov/ozone/title6/phaseout/hcfcfaqs.html
Material safety Data Sheet
http://www.honeywell.com/sites/docs/doc19194b8-fb3ebe9312-3e3e4447ab3472a0c2a5e5fdc1e6517d.pdf
Myths about R-410A
http://www51.honeywell.com/sm/410a/myths.html
Definitions of Section 608 Terms
http://www.epa.gov/ozone/title6/608/608defns.html#technician
Complying With The Section 608 Refrigerant Recycling Rule
http://www.epa.gov/ozone/title6/608/608fact.html#techcert
Overview of EPA Certification Test
http://www.epa.gov/ozone/title6/608/technicians/certoutl.html
Section 608 Technician Certification Programs
http://www.epa.gov/ozone/title6/608/technicians/608certs.html
Summary of Contents for AF-S100RX
Page 8: ......