8.7.2.2.1 -
Qmax (m3/h)
Set the flow measurement 100%. This value adjusts the analog output end scale
(20mA) and the frequency output end scale.
The range is related to the sensor DN.
Press the
key from run mode: the display will be as shown here next.
With
or
change the digit, with
moves the cursor.
Press
to confirm, the display will be as shown here next.
press the
key to exit and confirm the selection; press the
key to exit and
delete the selection.
8.7.2.2.2 -
LowCutoff %
Low Cutoff specifies the Qmax% value below which the instantaneous flow
measurement reading (direct or reverse) and the outputs are forced to zero.
Default: 0.0
Range: 0.0÷9.9
Press the
key from run mode: the display will be as shown here next.
With
or
change the digit, with
moves the cursor.
Press
to confirm, the display will be as shown here next.
press the
key to exit and confirm the selection; press the
key to exit and
delete the selection.
8.7.2.2.3 -
Max Limit %
When the measure variation is lower than Max Limit%, or higher but with a lower time period
than that set in Limit Time (s), the measure is not detected. When the measure variation is
higher than Max Limit% and with a higher time period than that set in Limit Time (s), the
measure is detected. Default: 0.0;
Range: 0.0÷9.9
Press the
key from run mode: the display will be as shown here next.
With
or
change the digit, with
moves the cursor.
Press
to confirm, the display will be as shown here next.
press the
key to exit and confirm the selection; press the
key to exit and
delete the selection.
8.7.2.2.4 -
Limit Time (s)
Sets the time limit used by the function Max Limit%.
Default: 00.0
Range: 00.0÷99.9
Press the
key from run mode: the display will be as shown here next.
With
or
change the digit, with
moves the cursor.
Press
to confirm, the display will be as shown here next.
press the
key to exit and confirm the selection; press the
key to exit and
delete the selection.
Pmag
- Setting