Operation
MOVIFIT® MC status LEDs
Operating Instructions – MOVIFIT
®
MC
136
7.1.5
Bus-specific LEDs for Modbus/TCP and EtherNet/IP™
This chapter describes the bus-specific LEDs for Modbus/TCP and EtherNet/IP™. In
the following figure, the LEDs are shown as dark:
DI03
DI01 DI02
DI00
DI04 DI05 DI06 DI07
DI08 DI09 DI10 DI1
1
DI12/DO00
DI13/DO01
DI14/DO02
DI15/DO03
®
MOVIFIT
SF/USR
RUN
ST
O
24V
-C
24V
-S
MS NS link/act1
link/act2
1033706507
LEDs "MS" and "NS"
The following table shows the statuses of LEDs "MS" (module status) and "NS" (net-
work status):
LED
MS
LED
NS
Meaning
Measure
Off
Off
MOVIFIT
®
not ready for oper-
ation.
No DC 24 V supply.
• Check DC 24 V supply.
• Switch on MOVIFIT
®
again.
• Exchange EBOX if problem
occurs repeatedly.
Red/
green
Flashing
Red/
green
Flashing
MOVIFIT
®
performs an LED
test.
This status should only be ac-
tivated briefly during the run-
up.
-
Red
Flashing
Red
Illumina-
ted
Conflict detected while as-
signing the IP address.
Another station in the network
is using the same IP address.
• Check whether there is a unit
in the network with the same
IP address.
• Change the MOVIFIT
®
IP ad-
dress.
• Check DHCP settings for IP
address assignment of the
DHCP server
(only if a DHCP server is
used).
Red
Illumina-
ted
X
Fault in MOVIFIT
®
assembly
hardware.
• Switch on MOVIFIT
®
again.
• Reset MOVIFIT
®
to the facto-
ry settings.
• Exchange EBOX if problem
occurs repeatedly.
Green
Flashing
Green
Flashing
Starting application.
-
19484828/EN – 01/2015