8
Operation
Status and error messages
Operating Instructions – MOVIPRO
®
PHE..B-A15-.1X0..B-00
75
Code
Meaning
Possible cause
Measure
612
Error while writing
M12 parameter
memory
•
M12 parameter memory not
plugged in or not plugged in
correctly
•
Plug in the M12 parameter memory
correctly.
•
Incompatible M12 parameter
memory connected
•
Connect compatible M12 parameter
memory.
•
M12 parameter memory de-
fective
•
Replace M12 parameter memory.
613
Plausibility monitor-
ing
•
Interruptions or crossfaults in
wiring to signal source
•
Check signal source.
UPd
614
Transfer drive para-
meters
•
The motor data was paramet-
erized or changed.
•
No measures required.
Code does not indicate an error. The
new motor parameters are trans-
ferred. The process takes approx. 10
seconds. Then, the device starts
automatic operation.
698
M12 parameter
memory replaced
•
M12 parameter memory re-
placed
•
No measures required. Code does
not indicate an error. The code
serves to distinguish between old
and new errors in the error history
and is not displayed on the device.
LEx
Unwanted or too
long applied signal
combinations for
speed limitation.
•
Signal source
•
Check signal source.
x = the row in the list "Speed limitation"
that caused the error. The row count
starts at 0.
PSE
XXX
Memory error
•
Internal error
•
Contact SEW‑EURODRIVE.
Depending on the parameterization, the errors of the table above are displayed as
error number (detailed error display) or error group (compressed error display). See
chapter 'Special functions' tab.
The error groups have the following meaning:
Error group
Meaning
Code
651
Error motor connection
317, 322
652
Overloads
303, 313, 314, 318, 323
653
Frequency inverter defective
302, 312
654
Other error
304, 308, 309, 320, 321
23576855/EN – 10/2017