8
Operation
Status and error messages
Operating Instructions – MOVIPRO
®
PHE..B-A15-.1X0..B-00
74
Code
Meaning
Possible cause
Measure
322
Overcurrent
•
Short circuit at frequency in-
verter output
•
Check the connection between the
frequency inverter output and the
motor as well as the motor winding
for short circuits.
•
Reset the error by switching off the
24 V supply voltage or via error re-
set.
323
Thermal brake over-
load
•
Line voltage too high
•
Select suitable line voltage.
•
Grid very asymmetrical
•
Check symmetry of the grid. Elimin-
ate unbalanced load.
•
Braking power too high
•
Wrong brake type selected
•
Reduce braking power. Increase
ramp time.
601
Distance sensor off-
line
•
Distance sensor defective
•
Replace distance sensor.
•
Distance sensor not connec-
ted
•
Check wiring.
607
Phase failure
•
Error in the current supply
•
Check supply cables including con-
ductor rail, current collectors and
device connection for phase failure.
•
Reset error by switching the device
off or via error reset function.
608
Infrared connection
canceled
•
Infrared connection to keypad
physically interrupted for more
than 15 s
•
Establish infrared connection via
keypad.
OFF
609
Operating switch
switched off
•
Operating switch switched off
•
Switch on operating switch.
•
Interruption of external operat-
ing switch connection
•
Check wiring of external operating
switch.
610
M12 parameter
memory connection
M12 parameter memory connec-
ted or disconnected during opera-
tion
•
Ensure that the M12 parameter
memory is always correctly connec-
ted during operation.
•
Check that the union nut on the M12
parameter memory unit is positioned
securely.
•
Only remove the M12 parameter
memory when the device is discon-
nected from the voltage. Insert the
M12 parameter memory again before
starting up the device.
•
Reset the error by switching off the
operating switch.
611
Error while reading
M12 parameter
memory
•
M12 parameter memory not
plugged in or not plugged in
correctly
•
Plug in the M12 parameter memory
correctly.
•
Data on M12 parameter
memory faulty
•
Write new M12 parameter memory.
•
Incompatible M12 parameter
memory connected
•
Connect compatible M12 parameter
memory.
•
M12 parameter memory de-
fective
•
Replace M12 parameter memory.
23576855/EN – 10/2017