7.1.3
Bus-specific LEDs for DeviceNet
This section describes the bus-specific LEDs for DeviceNet. In the following figure, the
LEDs are shown as dark:
"Mod/Net" LED
The function of the "Mod/Net" LED described in the following table is specified in the
DeviceNet specification.
836125963
DI02
DI01
DI00
DI03
DI04
DI06/DO0
0
DI07/DO0
1
DI05
RUN PS
MOVIFIT
®
24V
-C
24V
-S
SF/USR
BUS-F
Mod/Net
PIO
BIO
Mod/Net
Status
Meaning
Remedy
Off
Not switched
on / off-line
•
Unit is offline.
•
Unit performs DUP MAC check.
•
Unit is switched off.
•
Apply supply voltage via
DeviceNet connector.
Flashing
green
(1 s
cycle)
Online and in
operational
mode
•
The unit is online and no connection
has been established.
•
DUP-MAC check performed success-
fully
•
A connection to a master has not yet
been established.
•
Missing (incorrect) or incomplete
configuration
•
Include the station in the
master's scan list and start
communication in the
master.
Green
Online, opera-
tional mode
and connected
•
Unit is online.
•
Connection is active (established
state).
-
Flashing
red
(1 s
cycle)
Minor fault or
connection
timeout
•
A correctable fault has occurred.
•
Polled I/O and/or bit-strobe I/O connec-
tions are in the timeout status.
•
A correctable fault has occurred in the
unit.
•
Check the DeviceNet
cable.
•
Check the timeout
response (P831). If a
response with fault is set,
reset the unit once the
fault has been corrected.
Red
Critical fault or
critical link
failure
•
A fault that cannot be corrected has
occurred.
•
Bus off status
•
DUP-MAC check has detected a fault.
•
Check the DeviceNet
cable.
•
Check the slave address
(MAC ID). Is another unit
already using the same
address?