SEW-Eurodrive MOVIDRIVE MDR60A1320-503-01 Operating Instructions Manual Download Page 25

7

Technical data

Current carrying capacity

Addendum to the Operating Instructions – MOVIDRIVE

®

 MDR60A1320-503-01 regenerative power supply

25

7.3

Current carrying capacity

Device type

Driving operation

Braking operation

Free-wheeling diodes

IGBT modules

I

eff phase

I

eff phase

100%

1 min in

10 min

100%

1 min in

10 min

MDR60A 1320-503-01

260 A

360 A

260 A

330 A

INFORMATION

Just  like  the  input  of  a  drive  controller,  the  incoming  side  of  the  MOVIDRIVE

®

MDR60A1320-503-01  is  not  overload  protected.  Make  sure  during  dimensioning
that  the  maximum  DC  input  current  of  the  driver  controller  (including  overload
factor) does not exceed the input current of the regenerative power supply unit. If
that  is  the  case  nevertheless,  the  programmable  motor  current  limit  of  the  drive
controller should be identical to that of the regenerative power supply unit. You will
have to take the overload factor of the drive controller into consideration in this in-
stance as well.

Keep in mind when determining the regenerative power that the actual current re-
generative power always depends on the actually existing line voltage.

7.4

Fuses and cable cross sections

The line connection of the regenerative power supply unit takes place via terminals L1,
L2  and  L3  at  the  commutation  choke  and  PE  on  the  heat  sink.  Match  the  input  fuse
according to the current carrying capacity of the permitted connection lead. The listed
manufacturers  are  recommendations  only;  you  can  certainly  use  comparable  types
from other manufacturers.

7.4.1

Fuses to connect to incoming cable

Connect the semiconductor fuses listed in the following table to the incoming cable in
the regenerative power supply unit.

Device type

Max. back-up fuse

Connection/max. cable cross sec-
tion of supply cable

MOVIDRIVE

®

MDR60A1320-503-01

Siba 20 713 32.500

AC 500 A/AC
1100 V/110 mm
NH01

M10/150 mm

2

 terminal studs

27789314/EN – 07/2022

Summary of Contents for MOVIDRIVE MDR60A1320-503-01

Page 1: ...27789314_0722 Drive Technology Drive Automation System Integration Services Addendum to the Operating Instructions MOVIDRIVE MDR60A1320 503 01 regenerative power supply Edition 07 2022 27789314 EN...

Page 2: ...SEW EURODRIVE Driving the world...

Page 3: ...ype designation 6 3 Electrical installation 8 3 1 Installation in a CE typical drive system 8 3 2 Electrical connection 9 3 3 Control connections 13 3 4 Terminal assignment control terminal strip X2 1...

Page 4: ...2 Structure of the safety notes 1 2 1 Meaning of signal words The following table shows the grading and meaning of the signal words for safety notes Signal word Meaning Consequences if disregarded DA...

Page 5: ...ocument only in connection with the operating instructions Always use the latest edition of the documentation and the software The SEW EURODRIVE website www sew eurodrive com provides a wide selection...

Page 6: ...of several drive controllers possible Power section with high efficiency and operational safety Automatic system synchronization Overload protection in regenerative operation Monitoring of line voltag...

Page 7: ...e type 60 60 Type designation up to size 6 61 Type designation for size 7 Version A A Version status up to size 6 B Version status for size 7 Recommended inverter 1320 1320 132 kW Connection voltage 5...

Page 8: ...may be electromagnetically impaired by the regenerative power supply units 3 1 2 Structure Establish a connection over a large area on the grounded mounting plates for the power supply and regenerati...

Page 9: ...nnection over a wide area that are important 3 1 6 Further information Regenerative power supply units are electrical operating resources for operation in in dustrial and commercial systems These unit...

Page 10: ...rtain phase sequence has to be observed for the power supply connections of the power section clockwise rotating field The unit comes equipped with a phase monitoring option If the phase monitoring de...

Page 11: ...IDRIVE MOVITRAC MOVIDRIVE MOVITRAC A1 A2 SKS 1 2 3 3 M PE M PE Do not connect Relay contacts Control electronics ext OFF ext ON RESET Blocking Energy recovery Affects line contactor Faulty DC link con...

Page 12: ...ignment control terminal strip X2 Do not route the control cables parallel to motor cables which emit interference Apply the shielding of the control cables over a wide area of the metal cable glands...

Page 13: ...or confirm faults X2 12 0 V 1 When the supply voltage is present the precharging of the DC link capacitors is complete 2 The relay drops out in the event of an OFF command via terminals X2 7 and X2 8...

Page 14: ...may be damaged Terminal Function Description X2 1 NC contact Isolated relay contacts1 and there is no collective fault the relay picks up 2 Collective fault signal switching capacity of the relay con...

Page 15: ...03 01 regenerative power supply 15 3 5 Terminal assignment inhibit input A1 A2 Terminal Function Description A1 Inhibit input 24 V Control voltage to inhibit the regenerative power supply path not iso...

Page 16: ...Switch on the supply system The unit is ready for operation after about 1 s 2 Check to make sure that the regenerative power supply unit is ready for operation The unit is ready for operation if only...

Page 17: ...OVIDRIVE MDX60 61B and a MOVITRAC inverter X13 X2 X12 DI DI 1 DI 2 DI 3 DI 4 DI 5 DCOM VO24 DGND ST11 ST12 DI DI 1 DI 2 DI 3 DI 4 DI 5TF VOTF 24VIO GND 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 X13 DI...

Page 18: ...gger a manual reset by using the reset pushbutton on the front panel chapter Operation displays of the MDR60A1320 503 01 DGND X12 X13 DGND 9 X2 12 11 10 9 8 7 6 5 4 3 2 1 MOVIDRIVE MDR60A1320 503 01 D...

Page 19: ...oard its function is assigned to the two color green orange LED in the cover off collective error phase failure overcurrent UcE operation overtemperature reset GN RD RD YE OG 1877453195 If a fault mes...

Page 20: ...nt UCE Red Overtem perature Orange Collective fault Yellow During initial startup During operation 1 X The unit is ready for opera tion after about 1 s Unit in operation In rest posi tion 2 X Unit rea...

Page 21: ...following materials are hazardous to health and the environment These materials must be collected and disposed of separately Oil and grease Collect used oil and grease separately according to type En...

Page 22: ...er supply is maintenance free Observe the chapter Technical repair 6 2 Check cooling air vents The cooling air vents can clog up in case of unclean ambient air Check the regenera tive power supply uni...

Page 23: ...09 125 EC The waste disposal of this product is performed in compliance with the WEEE Directive 2012 19 EU The China RoHS mark states compliance with Directive SJ T 11364 2014 for limiting the use of...

Page 24: ...to 780 V Nominal DC link current at nominal current Iline IDCL DC 324 A Max DC link current at nominal current Iline IDClink_max Motor mode DC 486 A Generator mode DC 410 A General MOVIDRIVE MDR60A132...

Page 25: ...y unit You will have to take the overload factor of the drive controller into consideration in this in stance as well Keep in mind when determining the regenerative power that the actual current re ge...

Page 26: ...1 NOTICE Contact SEW EURODRIVE in case the fuses are activated other protection mea sures may have been triggered in the unit Replace internal fuses with original equipment only WARNING Electric shock...

Page 27: ...7 Technical data Dimension sheet Addendum to the Operating Instructions MOVIDRIVE MDR60A1320 503 01 regenerative power supply 27 7 5 Dimension sheet 7 5 1 Size 6 38264150027 27789314 EN 07 2022...

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...SEW EURODRIVE Driving the world SEW EURODRIVE GmbH Co KG Ernst Blickle Str 42 76646 BRUCHSAL GERMANY Tel 49 7251 75 0 Fax 49 7251 75 1970 sew sew eurodrive com www sew eurodrive com...

Reviews: