5
Service
Operating displays
Addendum to the Operating Instructions – MOVIDRIVE
®
MDR60A1320-503-01 regenerative power supply
20
5.2.1
U
CE
disconnection
The regenerative power supply unit switches off via the U
CE
protective device if the
maximum current specified for the respective unit is exceeded. The operating principle
of this protective device does, however, cause an overload of the IGBTs for less than
a millisecond far in excess of its specifications for normal operation. This is not usually
a problem for the unit. If this overcurrent disconnection occurs often or regularly, the
result will be an accelerated aging of the power semiconductors and ultimately prema-
ture failure of the component.
Frequent U
CE
disconnections due to overcurrents can be triggered by:
•
Overload
•
Undervoltage in the supply system
•
Defective or oscillating controller, such as in the drive controller
•
An oscillating reference value of the controller
•
Incorrect dimensioning of the system
5.2.2
LED signals
Fault
code
LED displays
Meaning
Relay
status
Opera-
tion
(Green)
Phase
failure
(Red)
Over-
cur-
rent /
UCE
(Red)
Overtem-
perature
(Orange)
Collective
fault
(Yellow)
During initial startup
During operation
1
X
-
-
-
-
The unit is ready for opera-
tion (after about 1 s)
Unit in operation
In rest posi-
tion
2
X
-
-
-
-
Unit ready for operation but no regenerative power supply
→ check DC fuses
3
X
-
-
X
X
-
Overtemperature of the heat
sink.
→ Fault message cannot be
confirmed while temperature
is still too high.
Dropped out
4
X
-
-
-
X
-
Just like fault code 3.
→ Heat sink temperature has
dropped and fault can be con-
firmed.
5
X
-
-
-
X
Unit has been turned off (external OFF).
→ Enable signal required
6
X
-
-
-
X
Triggering the overvoltage monitoring.
Enable signal is required if the line voltage has dropped to
nominal value
7
X
X
-
-
X
Incorrect rotating field or
phase
Phase failure has been de-
tected
→ Confirmation necessary.
8
X
-
X
-
X
-
Overcurrent (three-phase
side) has been detected.
→ Confirmation necessary.
9
X
X
X
-
X
Fault codes 7 and 8
Overcurrent has been detect-
ed with simultaneous phase
failure detection due to com-
mutation notch.
10
X
X
X
X
X
Several faults occurring at the same time.
11
-
-
-
-
-
Unit not operating, at least 2 phases without voltage.
13
X
X
-
-
-
-
Massive commutation notch
has been detected, no dis-
connection because jumpers
3 and 7 are open.
→ Operation can be re-
sumed, recommendation for
improved supply system.
27789314/EN – 07/2022