20
Operating Instructions – 10 kW Supply Module with Integrated Braking Resistor
5
General information
Startup
5
Startup
5.1
General information
Prerequisite
The drive must be configured correctly to ensure that startup is successful. Refer to the
MOVIAXIS
®
MX project planning manual for detailed project planning notes and an
explanation of the parameters.
For starting up the entire axis system, observe chapter "Startup" in the "MOVIAXIS
®
MX
Multi-Axis Servo Inverter" operating instructions.
Mains connection of axis system
HAZARD!
Uncovered power connections.
Severe or fatal injuries from electric shock.
• Install the touch guard according to the regulations.
• Never start the unit if the touch guard is not installed.
STOP!
• Observe a minimum switch-off time of 10 s for the relay K11.
• Do not turn the mains supply on or off
more than once per
minute!
Irreparable damage to the unit or unforeseeable malfunctions.
The specified times and intervals must be observed.