Appendix A
– Connecting to Rockwell Ethernet I/P PLC
10
Manual
– ECDriveS®
41
Once you have created and configured the new module, you can see the data tags creat-
ed your Controller Tags view as shown below.
For example, if you populate bits 0 thru 3 in C.
Data[0] with a “1”; by referencing the chart
in section
Fehler! Verweisquelle konnte nicht gefunden werden.
on page
Fehler!
Textmarke nicht definiert.
, this data configures Pin 2 on each Port to be a digital output.
Please note that RSLogix 5000, by default, creates an array tag of “SINT[400]” for the
Configuration Assembly for any Generic Ethernet Module. When the program is actually
downloaded to the PLC processor and begins communications with ECIO; the data ex-
changed will be the quantity of bytes entered when the module was created. For ECIO
this is Configuration Assembly Instance 128 with a size of 10 bytes as shown in the figure
New Module Configuration Screen.