Example 2:
E.g. offi ces

DIP switch settings:

1

2

3

4

On x

x

Off

x

The light 

must

 be switched on via the operating button and is 

daylight-independent. ECO Off and long press deactivated.

Automatic off via detector after end of cut-off time (Auto Off) or 
light level. Light sensor has fi rst priority. 

The light switches off automatically after a predetermined period 
when registration of activity in the detector’s coverage area has 
ceased, or the light level remains above the preset level for fi ve 
minutes.
230 V operating button must be connected.

Setting the light level and cut-off time is performed via the 
integrated potentiometers or via the IR remote control 41-926 
(accessory).

Example 3:
E.g. staircases

DIP switch settings:

1

2

3

4

On x

x

x

Off

 

 

Automatic on/off via daylight-dependent sensor. Light sensor has 
fi rst priority.

The light switches on automatically when the detector detects 
activity within the coverage range and the light level is below the 
preset level. 

The light switches off automatically after a predetermined period 
when registration of activity in the detector’s coverage area has 
ceased, or the light level remains above the preset level for fi ve 
minutes.

The light can 

always

 be switched on via the operating button, 

regardless of the daylight level. 

230 V operating button must be connected.

Setting the light level and cut-off time is performed via the 
integrated potentiometers or via the IR remote control 41-926 
(accessory).

  Operation & maintenance

Dirt affects the operation of the detector and the detector’s lens 
must therefore be kept clean. Use a damp cloth for cleaning. Use 
water mixed with ordinary detergent. Avoid putting pressure on 
the lens. If the lens or other parts of the detector are defective, it/
they must be replaced.

Technical data

Input:
Power supply ............................................. 230 V AC 50 Hz ±10%
Power consumption .................................. 0.2 W

Output:
Relay, potential-free .................................. NO, 230 V, µ 10 A
Load:
 Incandescent 

lamps 

............................. 2,300 W

 

Fluorescent tubes, uncompensated .... 1,200 VA

 

Halogen incandescent lamps .............. 2,300 W

Max. compensation capacity .................... 140 µF
Max. starting peak ..................................... 165 A/20 m sec.

Performance:
Lux range (preset settings) ........................ 20–1,000 lux 
Time range (preset settings) ...................... Pulse, 2–60 min. 
Range ........................................................ Ø20 m, 360°
Installation height ...................................... 2–3.4 m
Sensitivity  ................................................. 4 settings
Enclosure class ......................................... IP 54
Cable dimension (Ø14 mm max.) .............. 3 pcs. 5 x 2.5 mm

²

 

Ambient temperature ................................. -5°C to +50°C

Certifi cation:
CE in accordance with .............................. EN 60669-2-1

Accessories

IR Remote .................................................. 41-926
Presence detector, slave ........................... 41-702

Remote control

Settings using IR remote control: 

Fig. 8.

Lock/unlock:
Press three times to “unlock the sensor” – edit mode. Each press 
is indicated by a green fl ash in the detector. When the detector 
enters programming mode, this is indicated by one green fl ash.

The detector acknowledges with two fl ashes from the green LED. 
Press Lock/Unlock 3 times within 5 seconds. 

Press once to “lock the sensor” – operating mode. The detector 
acknowledges with two fl ashes from the green LED.

For all settings (except Light On/Off, Short push, Long push, 
Status Ch 1, Status Ch 2 and LED On/Off) the detector must be 
unlocked, the setting selected and then the detector must be 
locked again for the setting to become active.

If the detector is not locked, it will lock automatically after two 
minutes and any modifi ed settings will be saved.

Light On/Off (1 & 2):
This function turns the light on/off constantly, independently of 
registered activity and light level. If this function is activated, the 
red LED will fl ash On 0.25 sec. and Off 10 sec. 

The detector will remain in the selected function until it is 
cancelled again, either by pressing “Light On/Off” three times 

GB

Summary of Contents for 5703102207630

Page 1: ...ar efter ca 40 sek opvarmningstid Den r de LED blinker under opvarmning Opvarmningstidens afslutning indikeres med 2 korte blink fra den gr nne LED Tilslutningsskema Fig 5 Ordliste App Applikation den...

Page 2: ...r sensoren registrerer aktivitet i d kningsomr det og belysningsniveauet er under indstillet v rdi Lyset slukker automatisk efter en forudbestemt tid n r registre ring af aktivitet i sensorens d kning...

Page 3: ...betjening Indstillinger via IR fjernbetjening Fig 8 Lock unlock Der trykkes 3 gange for at l se unlock sensoren op indstillingsmode Hvert tryk indikeres med gr nt blink i sensoren N r sensoren er i pr...

Page 4: ...k On og 30 sek Off Alle vrige funktioner er blokeret For at oph ve funktionen inden de 8 timer er g et aktiveres 8 Hours igen n r sensoren er l st op Unlock Den r de LED stopper med at blinke og senso...

Page 5: ...n A S Tel 45 7442 4726 Fax 45 7442 4035 info servodan dk www servodan com Fig 4 27 46 4 100 Gasket for IP54 Fig 3 Fig 1 30 Fig 2 24 m 6 m 3 4 m 9 m2 13 5 m 140 m2 2 5 m 0 8 m 20 m 300 m2 3 m 6 m 28 m2...

Page 6: ...e d faut ou de perturbation du fonctionnement contacter un installateur lectricien agr Sous r serve de modifications Fig 5 Fig 7 Fig 6 Fig 8 Fig 9 41 700 Presence detector 360 1ch L1 L2 N L1 L1 L1 L1...

Page 7: ...the power supply the detector will be ready to operate after approximately 40 seconds warm up time The red LED flashes during warm up The end of the warm up time is indicated with two short flashes f...

Page 8: ...d when the detector detects movement the red LED and connected lighting will switch on for five seconds NB The walk test is daylight independent Examples Example 1 E g classroom DIP switch settings 1...

Page 9: ...gent Avoid putting pressure on the lens If the lens or other parts of the detector are defective it they must be replaced Technical data Input Power supply 230 V AC 50 Hz 10 Power consumption 0 2 W Ou...

Page 10: ...gs Pulse 2 min 5 min 10 min 15 min 30 min and 60 min There is also an eight hour 8 Hours constant illumination for operating a ventilation system HVAC system The detector must be unlocked Unlock first...

Page 11: ...b 4 Anschluss Der Melder darf erst an Spannung angeschlossen werden wenn alle Leitungsverbindungen angeschlossen sind Nach dem Anschluss der Spannung ist der Melder nach ca 40 Sek Aufw rmzeit betriebs...

Page 12: ...7 Test Um zu kontrollieren ob der Melder Bewegungen korrekt erkennt kann ein sogenannter Geh Test durchgef hrt werden Sie k nnen den Geh Test entweder ber das Time Potentiometer Minimumposition oder...

Page 13: ...vom Tageslichtniveau immer mit dem Bet tigungsdrucktaster eingeschaltet werden 230 V Bet tigungsdrucktaster muss angeschlossen werden Die Einstellung des Lichtniveaus und der Ausschaltverz gerung wird...

Page 14: ...Licht eingeschaltet werden soll weil das Tageslicht im Raum nicht mehr ausreicht Time Zeit Tasten Einstellen der Ausschaltverz gerung Es gibt 7 feste Einstellungen Pulse 2 Min 5 Min 10 Min 15 Min 30 M...

Page 15: ...europ en ou PL Fig 4 Raccordement Le d tecteur ne doit tre mis sous tension que lorsque tous les raccordements ont t effectu s Apr s la mise sous tension le d tecteur est pr t fonctionner l issue de 4...

Page 16: ...le d tecteur fonctionne correctement il est possible de faire un test de bon fonctionnement S lectionner le test de bon fonctionnement soit via le potentiom tre Time position minimum soit via le bouto...

Page 17: ...ram trage du niveau de luminosit naturelle et de la temporisation de d connexion s effectue via les potentiom tres int gr s ou la t l commande IR 41 926 accessoire Exploitation et entretien La salet n...

Page 18: ...osit minimale souhait e au moment o l clairage doit s allumer du fait que la luminosit naturelle n est plus suffisante dans la pi ce Touches Time temporisation de d connexion R glage de la temporisati...

Reviews: