10(18)
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | [email protected] | www.servodan.com
GB
within 5 sec., or by pressing the “Short push” button once.
After this, the detector will return to automatic operation in
accordance with the confi gured settings.
LED On/Off:
When the functions "Long push" and "Light On/Off" are
activated, this is indicated via LED. To turn this indicator off, use
"LED On/Off".
Ch 1 and Ch 2 buttons:
To set the Lux and Time settings for channel 1, CH 1 must fi rst
be pressed.
Status Ch 1 and Status Ch 2:
If one of these buttons is activated, the detector will indicate
which settings it is operating from via LED indication.
Channel 1 = Red LED
Channel 2 = Blue LED, is not active.
Green LED indicates start status.
Example: Channel 1 is set to 300 Lux and 10 minute delay. If you
press the “Status Ch 1” button, the green LED will fl ash once,
then the red LED will fl ash fi ve times, the green once and then
the red four times.
The fi rst fi ve red fl ashes indicate the fi fth lux setting = 300 lux.
The following four red fl ashes indicate the fourth Time setting =
10 minutes.
Lux buttons:
Setting light level.
Press Ch 1 for setting channel 1 which is indicated by the red
LED.
There are 10 preset settings: 20/50/100/200/300/400/500/700/10
00 and
(light independent) as well as a user-defi ned light value
(Learn actual lux).
The user-defi ned Lux value functions in the 20–1000 Lux range.
When "Learn actual lux" is activated, the red LED will fl ash once
to indicate that the current light level is loading. If the light level
is outside of the range 20 - 1000 Lux, the minimum (20 Lux) or
maximum (1000 Lux) will be loaded.
This setting should be used when the desired minimum lighting
in the room has been reached (the time when the light will be
switched on due to insuffi cient daylight in the room).
Time buttons:
Setting the cut-out time.
There are seven preset settings: Pulse/2 min./5 min./10 min./15
min./30 min. and 60 min.
There is also an eight-hour (8 Hours) constant illumination for
operating a ventilation system (HVAC system).
The detector must be unlocked (Unlock) fi rst. Press “Ch 1”
followed by “8 Hours” to activate channel 1 and then press “8
Hours”. The function will become active when the sensor is
locked (Lock).
When this function is active, the red LED fl ashes (0.25 seconds
On and 30 seconds Off). All other functions are blocked.
To cancel the function before the eight hours have passed,
activate “8 Hours” again when the detector is unlocked (Unlock).
The red LED stops fl ashing and the detector returns to automatic
when the detector is locked (Lock). The detector also exits from
the eight-hour timer, returning to automatic; the light can now be
switched on according to the selected application.
Instead of selecting a normal delay, it is possible to choose the
"Pulse function", where the output pulses, i.e. fl ashes with a
fi xed rhythm.
Pulse is 5 seconds On and for 55 seconds Off.
The pulse function can be used e.g. to control ventilation
systems. The pulse function stops after the selected cut-off time,
after activity detection in the sensor's coverage area has ceased.
If this function is desired, fi rst press "Pulse", then press one of
the "Time" buttons (not "8 Hours").
Example: The "Pulse" and "5 min" buttons are activated
via remote control. This means that after the fi nal activity
registration, the sensor will pulse for fi ve minutes.
Fig. 9.
Test On/Off:
Activating walk-test.
When the test has been activated, the blue LED comes on. When
the detector detects activity in the coverage area, the red LED
and associated lighting will switch on for 5 seconds. The blue
LED is off when the associated lighting is on.
NB! The walk-test is daylight-independent.
Short push:
Has the same function (and limitations) as a short push given by
the operating button.
Long push:
Has the same function (and limitations) as a long push given by
the operating button.
Fact. setting:
Pressing this button immediately restores all settings to factory
settings.