Data Pro
P/N 10029355 Rev AE
Operation Manual
Page 36 of 92
Voltage
’
values. The recommendation is to keep ‘Auto Volt’ enabled for self-diagnostic checks and
optimum communication operation.
Follow the menu steps below to enable/disable the
AutoVolt
:
Menu
Interface Setup
Interface For Gauge
Config
AutoVolt
Edit
A message displays after its successful execution.
8.5.5.2 Target Signal (AutoVolt Target
)
When
‘
Autovolt
’
is enabled, th
e ‘
Target Signal
’
represents the desired signal level seen by the FIC
that is about ½ the desired tool voltage. The default
‘
Target Signal
’
is 9mA, which corresponds to 18V
desired tool voltage as set by the FIC controller.
Follow the menu steps below to change the
‘Target Signal’
:
Menu
Interface Setup
Interface for Gauge
Config
Target Signal
Edit
8.5.5.3 Line Volts (Starting Line Voltage)
If
‘
Auto Volt
’
is OFF,
‘
Line
’
and
‘
COM
’
voltages stay at their default settings. The user can try different
‘
Line
Volts
’
values to mitigate the gauge communication problems. The recommended minimum and
maximum Line Volt values are 15V and 27V respectively.
The combined ‘
Line
’
and ‘
COM
’
voltages
cannot exceed 33V as set by the FIC interface for the downhole gauge.
Follow the menu steps below to change the ‘
Line Voltage
’
:
Menu
Interface Setup
Interface For Gauge
Config
Line Voltage
Edit
8.5.5.4 COM Voltage (Communication Voltage)
A general rule is to set the ‘
COM’
voltage to ¼ of the Line voltage (for example, if Line voltage is set to
20, then set COM voltage to 5). The recommended minimum and maximum ‘
COM Volt’
settings are 3V
and 10V respectively. Follow the menu steps below to change the
COM
Voltage:
Menu
Interface Setup
Interface For Gauge
Config
COM Voltage
Edit
8.5.5.5 Address
(
FIC Slave Address
)
The installed FICs have Modbus slave
‘ID’ of 1 and 2. Change the FIC slave ID via following menu
steps:
Menu
Interface Setup
Interface For Gauge
Config
Address
Edit
The FIC Modbus slave ID configuration screen will show the allowed range of addresses. The user
enters the new address using the onboard keypad then selects ‘
Save
’. The application will show a
message after the successful change of the Modbus ID.