Figure 2) Detector circuit layout with HART module
For the complete description of HART module and HART communication, refer to the proper
technical manual.
WARNING!
1
1
11
22
33
44
55
66
JP1
+
-
A
B
4-20mA Signal with
HART Communication
JP4
1
6
JP6
JP5
JPS2
JPS3
JPC3
JPC2
JPC1
JPP1
S1
JPS2
:
Selection of activation event for Relay K2:
Closed on Pin 1-2 : ALARM 1 Selected
Closed on Pin 2-3 : ALARM 2 Selected (Default)
JPS3
:
Selection of activation event for Relay K3:
Closed on Pin 1-2 : ALARM 2 Selected
Closed on Pin 2-3 : ALARM 3 Selected (Default)
+
-
JPC1
: Select the contact NO/NC of the K1 relay
Closed 1-2: Normally closed contact (Default)
Closed 2-3: Normally open contact
Relays contacts on
1-2 : Relay K1
3-4 : Relay K2
5-5 : Relay K3
DLB1
,
DLB2
,
DLB3
:relays status
LED On Relay energized
LED Off Relay de-energized
JPP1
:
Global Operation Mode Setting of 3 Relays:
Open : Normally Energized Mode (Default)
Closed : Normally De-Energized Mode
RELAY K2
: User programmable
Default : ALARM 2.
RELAY K3
: User programmable
Default : ALARM 3.
RELAY K1:
FAULT
and external watch dog status
(Not programmable by the user)
JP5
: Connector for calibration keypad
H
K
S1
: SET S1 TOWARD
H
SIDE FOR NORMAL WORKING
WITH HART CONNECTION.
S1
: SET S1 TOWARD
K
SIDE FOR CALIBRATION WITH
KEYPAD.
POWER SUPPLY
RS485
1 2 3
1 2 3
JPC2
: Select the contact NO/NC of the K2 relay
Closed 1-2: Normally closed contact (Default)
Closed 2-3: Normally open contact
JPC3
: Select the contact NO/NC of the K3 relay
Closed 1-2: Normally closed contact (Default)
Closed 2-3: Normally open contact
JP
6 : connector for flat cable
from HART module board
DLB3
DLB2
DLB1
1
K3
K2
K1
1
1
2
3
4
5
JP4
terminal block
5.5 Detector configuration
The detector provides a 4-20 mA proportional output and a RS485 serial output. Optional
relay and HART cards can be integrated into the detector.
5.6 4-20 mA output connection
The detector is configured to have a 4-20 mA proportional output by default. For the con-
nection of the detector with the control unit and the power supply it is recommended:
³
The use of shielded cable conforming to EN /IEC 60332-3.
³
Wires’ cross section depends on the distance between the control panel and the detec-
tor: for a distance up to m 100 we advise a 3-core wire with cross section area of 0.75
mm2; for a distance between m 100 and 200 we recommend a 3-core wire with cross
section of 1.0 mm2; for a distance between m 200 and 300 we recommend a 3-core
wire with cross section 1.5 mm2.
³
Should any junctions be necessary on wires, please make sure there is no interruption
on the shield.