1.2 Gas detector identification
The SMART S-IS detector code consists of four parts that identify the various parts (see prod-
uct data sheet for further details):
SIS:
Intrinsically safe detector, SIS model.
Enclosure code:
4A or 2S depending on the detector enclosure.
Transmitter code:
21, 22, 23 o 24 depending on the electronics (type of display and
relay
cards).
Sensor head code:
a unique code for each sensor head depending on gas to be detect-
ed and full scale range.
1.3 Technical specifications
Table 1) Technical specifications of SMART S-IS gas detectors
Sensing element
Electrochemical cell
Gas and measurement
range
O2: 0-25% vol.
SO2: 0-20 ppm
NO2: 0-20 ppm
Cl2: 0-20 ppm o 0-5 ppm
HCl: 0-50 ppm
Predicted sensor lifetime 2/3 years
Power supply
12- 24 Vdc - 20% + 15%
Vmax
30 Vdc
Um
30 V
Maximum power
4,5 W
Control unit
Microprocessor 32 bit
Watch-dog
Internal and external for the microprocessor status control
Visual indications
8 alphanumeric characters display and 7 status LEDs
Max load resistance
200 Ω on the 4-20mA output line
Signal output
RS485 for MU+; analogue 4-20 output
Relay outputs (optional)
3 relays with tension free changeover contact 24 V-1 A
Auto zeroing routine
Zero drift compensation
Digital filter
Variable average on the sampled values
Repeatability
From ±2% to ±5% FS (depending on sensor type)
Accuracy
From ±2% to ±5% FS (depending on sensor type)
Warm-up time
120 s
Stabilization time
60 minutes
Storage temperature
0 / +20°C up to 6 months
Operating condition:
Temperature
Humidity
-20 / +50°C
15 / 90 %RH (non condensing)
SIS
Enclosure code
Transmitter code
Sensor head code
-