External Power Mode (Using the LCD Remote)
Bypass Relay
The loads attached to the inverter output will operate independently of the inverter on/off. If the inverter is left on
(standby mode), the built-in bypass relay will automatically cycle back and forth between “inverter power” mode and
“external power” mode depending on the availability of the external AC power line.
NOTE: There will be a short break in AC power as the inverter transitions to and from bypass and charger mode.
Battery Charger
The battery charger will engage automatically and independently of the inverter On/Off status. The 3-step charging
process modes are bulk, acceptance, and float.
NOTE: “Bulk” is the same as “constant current” and may be called “CC” mode. “Acceptance” is the same as
“constant voltage” and may be called “CV” mode.
Bulk Mode
Accept Mode
Float Mode
Cold Charging (LFP Only)
Monitor Mode (Lead-Acid Only)
CHGR - BULK MODE
12.3 VOLT, 50 AMP
CHGR - ACCEPT MODE
14.4 VOLT, 30 AMP
CHGR - FLOAT MODE
13.1 VOLT, 0 AMP
CHGR-.1C LIMIT
11.9VOLT, 0AMP
CHGR-MONITOR
XX.XVOLT, 0AMP