Document No.U086951

     

Date

Jan/11/2019 

 

 

 

FIGURE 9. INSTALLATION (D1 RECESSED ESCUTCHEON)

 

 

 

 

 

FIGURE 10. INSTALLATION (D2 RECESSED ESCUTCHEON)

 

 
 

CARE AND MAINTENANCE 

 

The following instructions must be implemented for the maintenance and service of the Model FR-QR. 

 

NOTES 

Wet pipe sprinkler systems must be maintained at a minimum temperature of 40°F / 4°C to prevent freezing and 
bursting of the pipe and/or sprinklers. 
Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result. 
Absence of the Outer Ring from the D1 or D2 Recessed Escutcheon, which is used to cover the clearance hole, can 
delay sprinkler operation in a fire situation. 
In preparation for maintenance of the fire protection system, permission to close the main control valve must be 
obtained from the proper authorities, and all affected parties by this action, and must be informed before the 
maintenance session can commence. 
Do NOT enclose any sprinklers within drapes, curtains, or valances. 
Do NOT hang anything from the sprinklers. 
Do NOT clean the sprinklers with soap and/or water, detergents, ammonia, cleaning fluids, or other chemicals. 
Remove dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently 
vacuuming with a soft bristle (i.e., dusting) brush attachment. 
Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire 
development and spread of these materials can reduce the ability of the sprinkler system to aid in the control of a fire 
involving such hazards.   
 
 
 
 

Summary of Contents for FR-QR

Page 1: ...as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities having jurisdiction In the event of this condi...

Page 2: ...Page 2 of 9 Document No U086951 Date Jan 11 2019 FIGURE 1 Model FR QR K5 6...

Page 3: ...s Quick Response Sprinklers 3 Listed by UL for use in Canada as Quick Response Sprinklers 4 Approved by FM as Quick Response Sprinklers OPERATION The sprinkler assemblies fusible link is comprised of...

Page 4: ...sition reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern Obstruction to Water Distribution Locations of sprinklers must follow the obstr...

Page 5: ...t the position Installing Procedure Install Model FR QR sprinklers by the steps and figures shown below Use only D1 or D2 Recessed Escutcheons with Model FR QR Pendent sprinklers Use of any other rece...

Page 6: ...Page 6 of 9 Document No U086951 Date Jan 11 2019 FIGURE 3 UPRIGHT PENDENT and RECESSED PENDENT SPRINKLERS FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH...

Page 7: ...e 7 of 9 Document No U086951 Date Jan 11 2019 FIGURE 6 PROTECTOR REMOVAL FIGURE 7 INSTALLATION SOCKET A 1 2 drive ratchet not included is required for use with the Socket FR H FIGURE 8 PROTECTOR REMOV...

Page 8: ...preparation for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be i...

Page 9: ...and the regulations of any other authorities having jurisdiction The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufac...

Reviews: