3 of 9 

Document No.U086951

     

Date

Jan/11/2019 

TABLE A

 

Type 

SIN 

Temperature 

Frame or Deflector Color Code

Approvals 

Remarks 

162°F

 72

℃)

None 

205°F

 96

℃)

White *

1

 

Upright SS2552 

286°F

141

℃)

Blue *

1

 

c

UL

us 

*

2,

 *

3

 

FM *

4

 

 

162°F

 72

℃)

None 

205°F

 96

℃)

White *

1

 

Pendent SS2551 

286°F

141

℃)

Blue *

1

 

c

UL

us 

*

2, 

*

3

 

FM *

4

 

 

162°F

 72

℃)

None 

205°F

 96

℃)

White *

1

 

c

UL

us 

*

2, 

*

3

 

FM *

4

 

Recessed 

Pendent 

SS2551 

286°F

141

℃)

Blue *

1

 

c

UL

us 

*

2, 

*

3

 

Installed with the D1 

Recessed Escutcheon 

of 1/2” total adjustment

162°F

 72

℃)

None 

205°F

 96

℃)

White *

1

 

Recessed 

Pendent 

SS2551 

286°F

141

℃)

Blue *

1

 

c

UL

us 

*

2, 

*

3

 

Installed with the D2 

Recessed Escutcheon 

of 3/4” total adjustment

*1.    Chrome Plated, White and Black Painted are indicated by a dot on the Deflector. 

(Frame arms are colored for Natural Brass). 

*2.    Listed by UL as Quick Response Sprinklers. 
*3.    Listed by UL for use in Canada as Quick Response Sprinklers. 
*4.    Approved by FM as Quick Response Sprinklers. 

 
 

OPERATION 

 
The sprinkler assemblies fusible link is comprised of two link halves that are joined together with a thin layer of solder. When 
the rated temperature is reached, the solder melts and the two link halves separate. This leads to the water flow to be 
distributed on the affected fire area. 
 

 

 

 

  FIGURE 2. OPERATION PROCESS (The figure is for illustrative purposes only) 

 
 

DESIGN CRITERIA 

 
The Model FR-QR, Upright, Pendent and Recessed Pendent Sprinklers are listed by UL and FM as quick response / standard 
coverage for use in accordance with NFPA. The herein stated rules for use and installation of Model FR-QR are provided by the 
manufacturer and must be strictly implemented for safe and full results. Only the D1 or D2 Recessed Escutcheon, as applicable, 
is to be used for recessed pendent installations. 
 

Summary of Contents for FR-QR

Page 1: ...as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities having jurisdiction In the event of this condi...

Page 2: ...Page 2 of 9 Document No U086951 Date Jan 11 2019 FIGURE 1 Model FR QR K5 6...

Page 3: ...s Quick Response Sprinklers 3 Listed by UL for use in Canada as Quick Response Sprinklers 4 Approved by FM as Quick Response Sprinklers OPERATION The sprinkler assemblies fusible link is comprised of...

Page 4: ...sition reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern Obstruction to Water Distribution Locations of sprinklers must follow the obstr...

Page 5: ...t the position Installing Procedure Install Model FR QR sprinklers by the steps and figures shown below Use only D1 or D2 Recessed Escutcheons with Model FR QR Pendent sprinklers Use of any other rece...

Page 6: ...Page 6 of 9 Document No U086951 Date Jan 11 2019 FIGURE 3 UPRIGHT PENDENT and RECESSED PENDENT SPRINKLERS FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH...

Page 7: ...e 7 of 9 Document No U086951 Date Jan 11 2019 FIGURE 6 PROTECTOR REMOVAL FIGURE 7 INSTALLATION SOCKET A 1 2 drive ratchet not included is required for use with the Socket FR H FIGURE 8 PROTECTOR REMOV...

Page 8: ...preparation for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be i...

Page 9: ...and the regulations of any other authorities having jurisdiction The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufac...

Reviews: