Page

5 of 9 

Document No.U086951

     

Date

Jan/11/2019 

INSTALLATION 

 
The Model FR-QR, Upright, Pendent, and Recessed Pendent Sprinklers must be installed in accordance with the following 
instructions: 
 

NOTES 

Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers 
which show deformation or cracking in either the Sprinkler or the Protector. 
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the 
potential for damage to the sprinklers that could cause improper operation or non-operation. 
The Protector must remain on the sprinkler during installation. After the installation is completed, the Protector must 
be removed to place the sprinkler in service. 
Use a torque of 7 to 14 ft·lbs (9.5 to 19.0 N·m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended 
maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler. 

Use only Wrench FR-S or Socket FR-H for installation of Model FR-QR sprinklers. Use of any other wrench or socket is 
prohibited and may cause damage to the sprinkler. 

Do not over or under tighten the sprinkler due to an inadequate adjustment of the D1 or D2 Recessed Escutcheon. 
Re-adjust the sprinkler fitting to correct the position.   

 

Installing Procedure 

Install Model FR-QR sprinklers by the steps and figures shown below. Use only D1 or D2 Recessed Escutcheons with Model 
FR-QR Pendent sprinklers. Use of any other recessed escutcheon is prohibited and may void the warranty and approvals. 

 

Model FR-QR Upright and Pendent Sprinkler 

Step 1 

Install Upright sprinklers in the upright position. Install Pendent sprinklers in the pendent position. (Ref. Figure 3 and 4) 

     

Step 2 

Apply pipe-thread sealant to the threads. Begin hand-tightening the sprinkler into the sprinkler fitting. 

     

Step 3 

Using the Wrench FR-S, tighten the sprinkler into the sprinkler fitting with a torque of 7 to 14 ft·lbs

 

(9.5 to 19.0 N·m). (Ref. 

Figure 5) 

 

Step 4 

Remove the Protector by hand. (Ref. Figure 6) 

 
 

Model FR-QR Recessed Pendent Sprinkler 

Step 1 

Install the Inner Ring of the D1 or D2 Recessed Escutcheon over the sprinkler threads. (Ref. Figure 3 and 4) 

 
Step 2 

Apply pipe-thread sealant to the threads. Begin hand-tightening the sprinkler into the sprinkler fitting in the pendent position. 

 
Step 3 

Using the Socket FR-H or Wrench FR-S, tighten the sprinkler into the sprinkler fitting with a torque of 7 to 14 ft·lbs

 

(9.5 to 19.0 

N·m). (Ref. Figure 5 and 7) 
A 1/2" drive ratchet (not included) is required for use with the Socket FR-H. 

 
Step 4 

Remove the Protector by hand. (Ref. Figure 8) 
Slide on the Outer Ring of the D1 or D2 Recessed Escutcheon over the Sprinkler and push the Outer Ring over the Inner 
Ring until its flange comes in contact with the ceiling. (Ref. Figure 9 and 10) 

 
 
 

Summary of Contents for FR-QR

Page 1: ...as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities having jurisdiction In the event of this condi...

Page 2: ...Page 2 of 9 Document No U086951 Date Jan 11 2019 FIGURE 1 Model FR QR K5 6...

Page 3: ...s Quick Response Sprinklers 3 Listed by UL for use in Canada as Quick Response Sprinklers 4 Approved by FM as Quick Response Sprinklers OPERATION The sprinkler assemblies fusible link is comprised of...

Page 4: ...sition reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern Obstruction to Water Distribution Locations of sprinklers must follow the obstr...

Page 5: ...t the position Installing Procedure Install Model FR QR sprinklers by the steps and figures shown below Use only D1 or D2 Recessed Escutcheons with Model FR QR Pendent sprinklers Use of any other rece...

Page 6: ...Page 6 of 9 Document No U086951 Date Jan 11 2019 FIGURE 3 UPRIGHT PENDENT and RECESSED PENDENT SPRINKLERS FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH...

Page 7: ...e 7 of 9 Document No U086951 Date Jan 11 2019 FIGURE 6 PROTECTOR REMOVAL FIGURE 7 INSTALLATION SOCKET A 1 2 drive ratchet not included is required for use with the Socket FR H FIGURE 8 PROTECTOR REMOV...

Page 8: ...preparation for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be i...

Page 9: ...and the regulations of any other authorities having jurisdiction The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufac...

Reviews: