Page
:
5 of 9
Document No.U086951
Date
:
Jan/11/2019
INSTALLATION
The Model FR-QR, Upright, Pendent, and Recessed Pendent Sprinklers must be installed in accordance with the following
instructions:
NOTES
Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers
which show deformation or cracking in either the Sprinkler or the Protector.
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the
potential for damage to the sprinklers that could cause improper operation or non-operation.
The Protector must remain on the sprinkler during installation. After the installation is completed, the Protector must
be removed to place the sprinkler in service.
Use a torque of 7 to 14 ft·lbs (9.5 to 19.0 N·m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended
maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler.
Use only Wrench FR-S or Socket FR-H for installation of Model FR-QR sprinklers. Use of any other wrench or socket is
prohibited and may cause damage to the sprinkler.
Do not over or under tighten the sprinkler due to an inadequate adjustment of the D1 or D2 Recessed Escutcheon.
Re-adjust the sprinkler fitting to correct the position.
Installing Procedure
Install Model FR-QR sprinklers by the steps and figures shown below. Use only D1 or D2 Recessed Escutcheons with Model
FR-QR Pendent sprinklers. Use of any other recessed escutcheon is prohibited and may void the warranty and approvals.
Model FR-QR Upright and Pendent Sprinkler
Step 1
Install Upright sprinklers in the upright position. Install Pendent sprinklers in the pendent position. (Ref. Figure 3 and 4)
Step 2
Apply pipe-thread sealant to the threads. Begin hand-tightening the sprinkler into the sprinkler fitting.
Step 3
Using the Wrench FR-S, tighten the sprinkler into the sprinkler fitting with a torque of 7 to 14 ft·lbs
(9.5 to 19.0 N·m). (Ref.
Figure 5)
Step 4
Remove the Protector by hand. (Ref. Figure 6)
Model FR-QR Recessed Pendent Sprinkler
Step 1
Install the Inner Ring of the D1 or D2 Recessed Escutcheon over the sprinkler threads. (Ref. Figure 3 and 4)
Step 2
Apply pipe-thread sealant to the threads. Begin hand-tightening the sprinkler into the sprinkler fitting in the pendent position.
Step 3
Using the Socket FR-H or Wrench FR-S, tighten the sprinkler into the sprinkler fitting with a torque of 7 to 14 ft·lbs
(9.5 to 19.0
N·m). (Ref. Figure 5 and 7)
A 1/2" drive ratchet (not included) is required for use with the Socket FR-H.
Step 4
Remove the Protector by hand. (Ref. Figure 8)
Slide on the Outer Ring of the D1 or D2 Recessed Escutcheon over the Sprinkler and push the Outer Ring over the Inner
Ring until its flange comes in contact with the ceiling. (Ref. Figure 9 and 10)