Getting started
16
Output ports / Plug X the function „Filter Motor” and the additional function “Var. Frequency
Dri”.
To assign a function to the water level sensor(s), select in the menu Sensors / S X / Position
to the location where the sensor is mounted. Is it in front of the drum, select “Pre-chamber”,
and is it mounted behind the drum, select “Filter-chamber”. The Pre-chamber defined sensor
starts flushing when the water level rises above the flush level, while the definition Filter-
chamber initiates the cleaning, when the water level falls below the flush level.
Check and eventually select the proper type of water level sensor connected to your
AQUACULTURE|CONTROL. If you are using the water level probe PS, select Sensors / S X /
Sensor Type the type: „PS-300-MA” while if you use the water level sensor EPS, select „EPS-
250-MA“.
If you have connected your circulation pump to the AQUACULTURE|CONTROL, assign the
function “Circulation pump” to the corresponding 230 V plug. You can now switch off (and
on) your circulation pump by pressing the button „STOP“.
After connecting your spray / jet / backwash pump to the AQUACULTURE|CONTROL, assign
the function “Spray pump” to the corresponding 230 V plug. If you have it connected via an
PowerSwitch or VFD at one of the actuator output ports, assign the function “Spray pump” to
this port.
Clean the filter by pressing the button „CLEAN FILTER“. After the cleaning process, check the
water level in your system. If the water level is correct, you have to set the water level
sensor(s) to zero (referencing). Go therefore in the menu to Sensors / S X / Sensor Referencing
and confirm with yes. This sets the relative water level to 0 cm (the absolute water level is
always the actual water level measured by the probe, while the relative water level refers to
this set zero condition).
Now, your system is ready for operation.
To achieve the most efficient operation, you have to configure all other filter-related settings
so that they fit to your filter, for example the cleaning duration, etc. You´ll find more
information in the chapter “Operation”.
Using the AQUACULTURE|CONTROL to switch outputs as a function
of sensor measurements – Short version
1.
Mount the AQUACULTURE|CONTROL at a protected location.
2.
Mount the sensor at its position and connnect the cable to one of the SENSOR plugs.
3.
Turn the AQUACULTURE|CONTROL on.