background image

5/8

ELECTRICAL CONNECTIONS

Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or 

the Z-PC-DINAL-17.5 accessory.

RS485 GND

 

RS485 A

 

RS485 B

 

Power Supply AC / +

 

Power Supply  AC / -

IDC 10

Back connector (IDC 10)

The illustration shows the meanings of the various 

IDC10 connector pins if signals are to be sent via 

them directly.

Power Supply AC

Ground

Power Supply AC

GNDSHL

DG

ND

CANL / B

CAN

L / A

DIP 

SWITCH

(1230 Ohm terminator)

Z-PC-DINAL2-17.5 accessory use

If the Z-PC-DINAL2-17.5 accessory is used, signals 

can be sent via terminal boards. The illustration 

shows the meaning of the various terminals and 

DIP-switch position (found in all supports for the DIN 

rail listed in Accessories) for the termination of the 

CAN network (not used for the Modbus network). 

GNDSHLD: 

Connection cable signal protection shield 

(recommended).

Power supply

Terminals 2 and 3 can be used to provide the module with power supply as an 

alternative to the connection using the Z-PC-DINx bus.

The power supply voltage must remain in the range of either 19 and 40V Vdc (any 

polarity), or 19 and 28V Vac.

The upper limits must not be exceeded as this can seriously damage the 

module

.

If the power supply source is not protected against overload, a safety fuse with a 1 A 

max permissible value must be installed in the power supply line.

Serial port 2: RS485 SW2 = OFF

Z- KEY WIFI has a serial port that can be set with the SW2 switch.

If switch SW2 is in the OFF position, the RS485 COM 2 port is available at terminals 

10-11-12. The illustration shows how to complete connections.

N.B.: the indication of the RS485 connection polarity is not standardised and in some 

devices may be inverted.

1

2

3

10

11

12

Serial port 2: RS232 SW2 = ON

Z- KEY WIFI has a serial port that can be set with the SW2 switch.

If switch SW2 is in the ON position, the RS232 COM 2 port is available at terminals 

10-11-12.

The illustration shows how to complete connections.

The RS232 interface is fully settable.

10

11

12

GND

A (+)

B (-)

GND

RX

TX

Vac/Vdc

Vac/Vdc

Summary of Contents for Z-KEY-WIFI

Page 1: ...Serial Device Server with WIFI SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals in other languages and the configuration software visit www sene...

Page 2: ...er countries with recycling The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste The module mus...

Page 3: ...icroSD card slot POWER SUPPLY Voltage 11 40 Vdc 19 28 Vac 50 60 Hz Absorption Typical 2 W 24Vdc Max 3 W 24 Vac WIFI IEEE 801 11 b g n Security WEP WPA WPA 2 COMMUNICATION PORTS RS242 or RS485 switchab...

Page 4: ...has a micro USB connector on the front panel and can be configured using applications and or software programs The USB serial port uses the following communication parameters 115200 8 N 1 The USB comm...

Page 5: ...vide the module with power supply as an alternative to the connection using the Z PC DINx bus The power supply voltage must remain in the range of either 19 and 40V Vdc any polarity or 19 and 28V Vac...

Page 6: ...ess Point function follow the following steps 1 Press the side button of the Z KEY WIFI 2 Keeping the button pressed power the instrument 3 Release the button after 5 seconds Through this procedure th...

Page 7: ...GURATION ACCESSORIES CODE DESCRIPTION KIT USB Programming KIT USB CD cable MICRO SD Micro SD Flash card CE RJ45 RJ45 R 1 5 m Ethernet cable CS DB9M MEF 1012 Z KEY RS232 DB9 serial connection cable Z P...

Page 8: ......

Reviews: