TECHNICAL SPECIFICATIONS
STANDARDS
Safety: EN60950, EN62311
Radio equipment device: EN301489-1 V2.1.1, EN301489-17 V3.1.1, EN300328 V2.1.1
Additional notes:
a 1 A delayed fuse must be installed near the module, in series with the
power supply connection.
INSULATION
ENVIRONMENTAL
CONDITIONS
T
emperature
:
-20 – + 70°C
Humidity
:
30%– 90% non condensing.
Altitude:
Up to 2000 m above sea level
Storage temperature:
-20 + 85°
Protection rating:
IP20.
ASSEMBLY
IEC EN60715, 35mm DIN rail in vertical position.
CONNECTIONS
3-way removable screw terminals, pitch 5 mm
Rear connector IDC10 for DIN bar 46277
RJ45 front connector
SMA antenna connector
front micro USB
microSD card slot
POWER SUPPLY
Voltage: 11 – 40 Vdc; 19 – 28 Vac 50 – 60 Hz
Absorption: Typical: 2 W @ 24Vdc, Max: 3 W @ 24 Vac
WIFI
IEEE 801.11 b/g/n
Security WEP / WPA / WPA 2
COMMUNICATION
PORTS
RS242 or RS485 switchable on terminal 10 - 11 - 12: Maximum baud rate 115 k, maximum
RS232 cable length <3m, ModBus RTU master / modBus RTU slave protocol.
RS485 IDC10 rear connector: Maximum baud rate 115 k, ModBus RTU master / ModBus
RTU slave protocol.
RJ45 front Ethernet connector: 10/100 Mbit/s, maximum distance 100 m with auto switch.
Micro SD
: plug-in: lateral micro USB
FACTORY IP ADDRESS
3/8
The default module IP address is static: 192.168.90.101
WEB SERVER
To access the maintenance Web Server with 192.168.90.101 factory IP address:
Default user: admin, Default password: admin, http://192.168.90.101
Power
Supply
1500 Vac
ETH
USB
Comm.
Comm.
RS485
RS485/232
(IDC10)
WIFI
Summary of Contents for Z-KEY-WIFI