User Manual
T201DCH50/100/300-M
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
Doc. MI004730-EN
Rev. 1.0.2
Page 14
FULL CONFIGURATION WITH EASY SETUP
For configure all the device parameters you must use the RS485 Port and the Easy T201DCH-M software
included in the Easy Setup Suite.
You can download the Easy Setup software for free from:
www.seneca.it
6.1.
Easy Setup Menu
Connect: Use the connect icon for connect the PC to the Device. Note that you need a RS485 to USB
converter like Seneca S117P1 or S107USB for connect the device to a PC.
New: Load the default parameters in the actual project
Open: Open a stored project
Save: Save the actual project
Read: Read the actual configuration from the device (if the dip switches are not ALL OFF the configuration is
read from dip switches)
WARNING!
If you read a configuration from the device with at least one dip switch to “ON” the software will read
the dip switch configuration because overwrite the flash configuration.
Send: Send the project configuration (if the dip switches are not ALL OFF the device use the dip switch
configuration and NOT the sent configuration)
Test: Start a Registers read, you can also reset the MIN/MAX values and start/stop a Datalogger
Value
Registers with Inverse
(MSW-LSW) Floating
Point
BE REPRODUCED WITHOUT PRIOR PERMISSION.