Safety options (frame):
Time
: sets the value of the safety timer whose time base is selectable between minutes and hours. If the radio
doesn’t receive a valid packet within the selected time interval, the digital output (relay) is forced to a condition
chosen in the field "Relays to Open/Closed". To disable the functionality of the safety timer set the value of
"Time" to zero.
Minute
: the value of "Time" is expressed in minutes.
Hours
: the value of "Time" is expressed in hours.
Relays to
Open
: when the safety timer expires, the relay contact of digital output will be forced to open.
Relays to
Closed
: when the safety timer expires, the relay contact of digital outputs will be forced to closed.
Its address:
It is the value of the address of the radiomodem. Each unit must have a unique address. This constraint applies
both to the Slaves and to the Master radiomodems.
Node address (Master unit):
It is the value of the target modbus node. Each node address is associated with the sequence of addresses of
the radiomodems through the routing table.
Routing table (double click of the mouse on "Target" or [Enter] key):
When the focus is on the "Node address" field, pressing the "Enter" key on the keyboard or by double clicking
the mouse, a window opens in which you can enter the sequence of radiomodem addresses to associate to a
particular node address.