Slave / Master
:
Allows you to select the functionality of the radiomodem between Master and Slave. The unit configured as
Master uses the energy saving and transmits as a result of events. The unit configured as a Slave is always
active and never takes the initiative of the transmission.
When a device is used as digipeater the device must be settled as Slave.
Cycle Update
:
In this field the time of the periodical transmission is set. The time base is selectable between seconds, minutes
or hours. The time range can vary from one second (minimum) to 255 hours (maximum). In this field you cannot
insert a value less than the value of the time interval assigned to the field "Sensor stabilization time".
Safety options (frame):
Time
: sets the value of the safety timer whose time base is selectable between minutes and hours. If the radio
doesn’t receive a valid packet within the selected time interval, the digital output (relay) is forced to a condition
chosen in the field "Relays to Open/Closed". To disable the functionality of the safety timer set the value of
"Time" to zero.
Minute
: the value of "Time" is expressed in minutes.
Hours
: the value of "Time" is expressed in hours.
Relays to
Open
: when the safety timer expires, the relay contact of digital output will be forced to open.
Relays to
Closed
: when the safety timer expires, the relay contact of digital outputs will be forced to closed.
Its address:
It is the value of the address of this radiomodem. It is advisable to configure each radiomodem with a unique
address.