INSTALLATION MANUAL
4/7
ELECTRICAL CONNECTIONS
The upper power supply limits must not be exceeded, as this could cause serious damage to the module.
Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc...).
CAUTION
21
22
20
–/
+ /
23 B(-)
24 A(+)
25 GND
POWER SUPPLY
RS485 SERIAL PORT
Connection to the RS485 port.
Polarity is not standardised
and in some devices may be
inverted.
ANALOGUE INPUTS:
The device has 8 analogue inputs that can be configured via DIP-SDWITCH:
CURRENT
(mA)
Transmitter active
VOLTAGE
(V) ±30V
THERMOCOUPLE
(Tc / mV)
B
A
C
+
mA
(40, 43,...60, 63)
CURRENT
(mA)
Passive transmitter,
with external power supply
DIGITAL INPUTS
(PNP)
With internal power
DIGITAL INPUTS
(PNP)
With external power
DIGITAL OUTPUTS
(PNP)
With external power
The relative dip-switch goes to the
ON position
The relative dip-switch goes to the
OFF position
The relative dip-switch goes to the
OFF position
The relative dip-switch goes to the
ON position
B
A( 40, 43,...60, 63)
C
+
TC/mV
B
A
C
+
(40, 43,...60, 63)
V
.......
B
A
C
S
mA
+
(40, 43, 46, 49)
ALIM.
EXT.
+
The digital outputs must be powered
externally to function properly.
10
11
12
....
17
18
19
+
52
53
10
11
12
....
17
18
19
LOAD
LOAD
LOAD
LOAD
LOAD
10
11
12
....
17
18
19
+