MI00531-2-EN

INSTALLATION MANUAL

5/7

INSTRUCTIONS FOR ANALOGUE INPUTS:

The analogue inputs of this device are designed to measure 

voltages/currents on floating circuits that is not electrically 

connected to each other. It is also possible to measure 

currents/voltages on non-floating circuits, with a potential 

difference between negative terminals not exceeding 

200 mV. In the case of measurement with thermocouples it 

is possible to obtain correct measurements even if they are 

applied to common metal parts.

The temperature measurement using thermocouples can be 

affected by measurement errors due to the determination of 

the cold junction temperature carried out near the terminal. 

To eliminate any measurement errors it is necessary to wire 

the thermocouples on an isothermal terminal board separate 

from the device as shown in the diagram on the side.

Input No. 1 set as Pt100 (see the table on page 4) will then 

be used to measure the cold junction temperature of said 

terminal block.

PT100

A 40

B 41 AI1

C 42

A 43

B 44

C 45

A ...

B ...

C ...

A 63

B 64

C 65

AI2

AI...

AI8

+

+

RAME

MORSETTIERA

ISOTERMA

RAME

RAME
RAME

TC

TC

ANALOGUE INPUTS

Range

Resolution

Impedance

Precision

Temperature drift Ext. current

Voltage (V)

-30+30 Vdc

1 mV

> 200 kohm

0.1% f.s.

100 ppm

Voltage (mV)

-120+120 mV

4 uV

> 10 Mohm

0.1% f.s.

100 ppm

Current (mA)

-24..-+24 mA

0.8 uA

20 Ohm

0.2% f.s.

100 ppm

Thermocouple

-120+120 mV

4 uV

> 10 Mohm

0.1% f.s.

100 ppm

PT100

-200..200 °C

0.05 °C

0.5°C

50 ppm

0.5 mA

THERMOCOUPLE TYPE

Range

[°C]

Resolution

[°C]

Impedance

[Mohm]

Precision

[f.s.]

Temperature

Drift

Standard cold junction 

error [°C]

J

-210..1200

0.1

> 10

0.1%

100ppm

EN 60584

2

K

-200..1372

0.1

> 10

0.1%

100ppm

EN 60584

2

T

-200..400

0.1

> 10

0.1%

100ppm

EN 60584

2

E

-200..1000

0.1

> 10

0.1%

100ppm

EN 60584

2

N

-200..1300

0.1

> 10

0.1%

100ppm

EN 60584

2

R

-50..1768

0.3

> 10

0.1%

100ppm

EN 60584

2

S

-50..1768

0.5

> 10

0.1%

100ppm

EN 60584

2

B

250..1820

0.5

> 10

0.1%

100ppm

EN 60584

2

L

-200..800

0.1

> 10

0.1%

100ppm

GOST:8.585

2

FEATURE SUMMARY

THERMORESISTANCE

The relative dip-switch goes to the 

OFF position.

Function valid only for analogue 

input 1.

The product is not suitable for connection to a dangerous voltage conductor. The maximum allowable voltage is 50 Vac.

WARNING

The input for the RTD thermoresistance is available only for the first channel. For channels 2 to 8 it is not available.

CAUTION

ISOTHERMAL 

TERMINAL BLOCK

COPPER
COPPER

COPPER
COPPER

Summary of Contents for R-8AI-8DIDO

Page 1: ...ny operation The module must only be used by qualified electricians Specific documentation is available using the QR CODE shown on page 1 Electrical and electronic waste disposal applicable in the Eur...

Page 2: ...s set Flashing Waiting for the IP address from the DHCP COM R 8AI 8DIDO P version only On Verification of RS485 connection Flashing Data packet transmission over RS485 FAIL On Digital output in FAIL O...

Page 3: ...IDO version only 2 Ethernet with LAN fault bypass function 100 base T on RJ45 1 RS485 port on terminals R 8AI 8DIDO version only AUXILIARY VOLTAGE OUTPUT Max voltage current 12 Vdc 20 mA DIGITAL INPUT...

Page 4: ...ome devices may be inverted ANALOGUE INPUTS The device has 8 analogue inputs that can be configured via DIP SDWITCH CURRENT mA Transmitter active VOLTAGE V 30V THERMOCOUPLE Tc mV B A C mA 40 43 60 63...

Page 5: ...ERA ISOTERMA RAME RAME RAME TC TC ANALOGUE INPUTS Range Resolution Impedance Precision Temperature drift Ext current Voltage V 30 30 Vdc 1 mV 200 kohm 0 1 f s 100 ppm Voltage mV 120 120 mV 4 uV 10 Moh...

Page 6: ...vice have the following functions DIP SWITCH positions DIP SWITCH SW1 AND SW2 ANALOGUE INPUT OUTPUT CONFIGURATION SW3 DIP SWITCH DEFAULT SETTINGS SETTING THE DIP SWITCHES SW1 SW2 1 2 3 4 1 2 3 4 AI1 A...

Page 7: ...s not interrupted and the devices downstream of the switched off one will still be accessible This function has a limited duration the connection remains active for a few days typically 4 The fault by...

Reviews: