background image

MI00531-2-EN

INSTALLATION MANUAL

3/7

CERTIFICATIONS

https://www.seneca.it/products/r-8ai-8dido/doc/CE_declaration

INSULATION

POWER SUPPLY

Voltage: 10÷40 Vdc; 19÷28 Vac; 50÷65 Hz; Absorption: 3 W

ENVIRONMENTAL

CONDITIONS

Operating temperature: 

from -25°C to +65 °C

Humidity: 10%– 90% non condensing.  

Storage temperature: from -30°C to +85 °C

Protection rating: IP20

ASSEMBLY

35mm DIN rail IEC EN60715

CONFIGURATION

With integrated WEB Server 

(R-8AI-8DIDO version only)

CONNECTIONS / 

COMMUNICATION

PORTS

3.5 mm pitch terminal block, 1.5 mm

max cable section

1 micro USB port for programming (R-8AI-8DIDO version only)

2 Ethernet (with LAN fault-bypass function) 100 base T on RJ45

1 RS485 port on terminals 

(R-8AI-8DIDO version only)

AUXILIARY VOLTAGE 

OUTPUT

Max voltage/current: 12 Vdc / 20 mA

DIGITAL INPUTS

Number of channels: 8; Voltage: Threshold ON: > 9 V; Threshold OFF: < 4 V; Vmax: 24 V;

 

Impedance 9 kΩ

DIGITAL OUTPUTS

Number of channels: 8, MOSFET, PNP; Max voltage/current: 0.2 A / 24 V

ANALOGUE

INPUT

Number of channels: 8; Type: voltage, current, thermocouple, thermoresistance

Measuring range:          Voltage: -30 V ÷ -30 V; -120m V ÷ +120 mV

                                      Current: -24 mA ÷ +24 mA

                                      Thermocouple: J, K, T, E, N, R, S, B, L

                                      Thermoresistance: PT100: -200 °C ÷ +200 °C

 

                                      (only for cold junction offset)

NOTE

: See page 6 for dip-switch settings

TECHNICAL SPECIFICATIONS

PWR

1500 Vac

DIGITAL

INPUT/OUTPUT

ANALOG INPUT

USB

RS485

ETH1

PORT1

ETH2

PORT2

PWR AUX

Summary of Contents for R-8AI-8DIDO

Page 1: ...ny operation The module must only be used by qualified electricians Specific documentation is available using the QR CODE shown on page 1 Electrical and electronic waste disposal applicable in the Eur...

Page 2: ...s set Flashing Waiting for the IP address from the DHCP COM R 8AI 8DIDO P version only On Verification of RS485 connection Flashing Data packet transmission over RS485 FAIL On Digital output in FAIL O...

Page 3: ...IDO version only 2 Ethernet with LAN fault bypass function 100 base T on RJ45 1 RS485 port on terminals R 8AI 8DIDO version only AUXILIARY VOLTAGE OUTPUT Max voltage current 12 Vdc 20 mA DIGITAL INPUT...

Page 4: ...ome devices may be inverted ANALOGUE INPUTS The device has 8 analogue inputs that can be configured via DIP SDWITCH CURRENT mA Transmitter active VOLTAGE V 30V THERMOCOUPLE Tc mV B A C mA 40 43 60 63...

Page 5: ...ERA ISOTERMA RAME RAME RAME TC TC ANALOGUE INPUTS Range Resolution Impedance Precision Temperature drift Ext current Voltage V 30 30 Vdc 1 mV 200 kohm 0 1 f s 100 ppm Voltage mV 120 120 mV 4 uV 10 Moh...

Page 6: ...vice have the following functions DIP SWITCH positions DIP SWITCH SW1 AND SW2 ANALOGUE INPUT OUTPUT CONFIGURATION SW3 DIP SWITCH DEFAULT SETTINGS SETTING THE DIP SWITCHES SW1 SW2 1 2 3 4 1 2 3 4 AI1 A...

Page 7: ...s not interrupted and the devices downstream of the switched off one will still be accessible This function has a limited duration the connection remains active for a few days typically 4 The fault by...