background image

ENGLISH - 7/8

Input

The module accepts input from a PT100 (EN 60 751) or NI100 temperature probe with
connection by 2, 3 or 4 wires.

The use of shield cables is recommended for the electronic connections.

2-wire connection

This is the connection to be used for short distances ( < 10 m) between module and probe,
bearing in mind that it adds an error (which may be removed by sofware programming)
equivalent to the resistance contributed by the connection cables to the measurement.
DIP-switch SW1-1 set in ON Position (2 / 4 wires) or all DIP-switches in OFF position
(configuration from memory: module programmed by PC for 2 wires connection).
With bridges between Terminals 1 and 2 and Terminals 3 and 4.

3-wire connection

This is the connection to be used for media-long distances ( > 10 m ) between module and
probe. The instrument performs compensation for the resistance of the connection cables.
In order for compensation to be correct, it is necessary that the resistance values of each
conductors be the same because in order to perform compensation the instrument
measures the resistance of only one conductor and assumes the resistance of the others
conductors to be exactly the same.
DIP-switch SW1-1 set in OFF Position (3 wires) or all DIP-switches in OFF position
(configuration from memory: module programmed by PC for 3 wires connection).
With bridge between Terminals 3 and 4.

4-wire connection

This connection to be used for media-long distances ( > 10 m ) between module and probe.
Provides the maximum precision because the instrument measure the resistance of the
sensor independently of the resistance of the connection cables

.

DIP-switch SW1-1 set in ON Position (2 / 4 wires) or all DIP-switches in OFF position
(configuration from memory: module programmed by PC for 2 wires connection).

1

5

6

7

8

2

3

4

OUTPUT

INPUT

RTD  4 wires

RTD  3 wires

RTD  2 wires

MI00124 -E

2

1

2

3

4

1

2

3

4

1

2

3

4

J

J

J

Summary of Contents for K120RTD

Page 1: ...nge Resistance Range Minimum span Current on sensor Cable resistance Connection Resolution 60 250 C 69 290 20 C 750 A rated m Max 25 per wire 2 3 or 4 wires 6 mW NI100 Input 5 30 V DC 4 20 mA 20 4 mA...

Page 2: ...ing error connection internal fault fault Spring terminals 0 2 2 5 mm 2 8 mm PBT black colour 6 2 x 93 1 x 102 5 mm 45 g Diagram Load Resistance vs Minimum Functioning Voltage RLoad W MI00124 E 2 Othe...

Page 3: ...Range 3 wires present NO PT100 0 C 100 C Towards the top of the output range YES a 2 5 over range value is acceptable a 5 over range value is considered a fault MI00124 E 2 SETTING BY DIP SWITCHES Con...

Page 4: ...R 2 SW1 Present Absent The filter slows down the response time to around 620 ms and guarantees the repeating of the disturbance signal at 50 60 Hz overlapping the measurement signal REVERSED OUTPUT 3...

Page 5: ...0 60 240 480 65 250 500 70 260 520 75 270 550 80 280 580 85 290 600 90 300 620 95 310 650 100 320 110 330 See the table below for the corresponding values Output signal limit Over range Fault 2 5 Faul...

Page 6: ...and Full scale values RTD Connection 2 wires 3 wires or 4 wires 50 60 Hz Rejection Absent or Present Measurement filter Absent or Present 1 2 5 10 30 60 seconds Output Normal 4 20 mA o Reversed 20 4 m...

Page 7: ...he resistance of the connection cables In order for compensation to be correct it is necessary that the resistance values of each conductors be the same because in order to perform compensation the in...

Page 8: ...to dispose of it Instead it should be handed over to an applicable collection point for the recycling of electrical and electronic equipment By ensuring this product is disposed of correctly you will...

Reviews: