ENGLISH - 5/8
OVER-RANGE (*)
8
SW2
YES: a 2.5% over-range value is acceptable;
a 5% over-range value is considered a fault.
NO: the fault alone causes a 2.5% over-range value.
MEASUREMENT FULL SCALE
1
1
SW2
SW2
1
SW2
2
2
2
3
3
3
4
4
4
5
5
5
6
6
6
°C
°C
°C
0
120
340
5
130
350
10
140
360
15
150
370
20
160
380
25
170
390
30
180
400
35
190
410
40
200
420
45
210
430
50
220
440
55
230
450
60
240
480
65
250
500
70
260
520
75
270
550
80
280
580
85
290
600
90
300
620
95
310
650
100
320
110
330
(*) See the table below for the corresponding values.
Output signal limit Over-range / Fault
±
2,5 %
Fault
±
5 %
20 mA
20,4 mA
21 mA
4 mA
3,6 mA
< 3,4 mA
OUTPUT SIGNAL IN CASE OF FAULT
7
SW2
Towards the top of the output range
Towards the bottom of the output range
MI00124 -E
2
Configuration by PC
The configuration by PC use is possible with the following accessories:
S117P: USB to RS232 / TTL
PM002411: connection cable between S117 and K120RTD
Z120: Dedicated programming software.