background image

ENGLISH - 5/8

OVER-RANGE (*)

8

SW2

YES: a 2.5% over-range value is acceptable;
a 5% over-range value is considered a fault.

NO: the fault alone causes a 2.5% over-range value.

MEASUREMENT FULL SCALE

1

1

SW2

SW2

1

SW2

2

2

2

3

3

3

4

4

4

5

5

5

6

6

6

°C

°C

°C

0

120

340

5

130

350

10

140

360

15

150

370

20

160

380

25

170

390

30

180

400

35

190

410

40

200

420

45

210

430

50

220

440

55

230

450

60

240

480

65

250

500

70

260

520

75

270

550

80

280

580

85

290

600

90

300

620

95

310

650

100

320

110

330

(*) See the table below for the corresponding values.

Output signal limit Over-range / Fault

±

2,5 %

Fault

±

5 %

20 mA

20,4 mA

21 mA

4 mA

3,6 mA

< 3,4 mA

OUTPUT SIGNAL IN CASE OF FAULT

7

SW2

Towards the top of the output range

Towards the bottom of the output range

MI00124 -E

2

Configuration by PC

The configuration by PC use is possible with the following accessories:
S117P: USB to RS232 / TTL
PM002411: connection cable between S117 and K120RTD
Z120: Dedicated programming software.

Summary of Contents for K120RTD

Page 1: ...nge Resistance Range Minimum span Current on sensor Cable resistance Connection Resolution 60 250 C 69 290 20 C 750 A rated m Max 25 per wire 2 3 or 4 wires 6 mW NI100 Input 5 30 V DC 4 20 mA 20 4 mA...

Page 2: ...ing error connection internal fault fault Spring terminals 0 2 2 5 mm 2 8 mm PBT black colour 6 2 x 93 1 x 102 5 mm 45 g Diagram Load Resistance vs Minimum Functioning Voltage RLoad W MI00124 E 2 Othe...

Page 3: ...Range 3 wires present NO PT100 0 C 100 C Towards the top of the output range YES a 2 5 over range value is acceptable a 5 over range value is considered a fault MI00124 E 2 SETTING BY DIP SWITCHES Con...

Page 4: ...R 2 SW1 Present Absent The filter slows down the response time to around 620 ms and guarantees the repeating of the disturbance signal at 50 60 Hz overlapping the measurement signal REVERSED OUTPUT 3...

Page 5: ...0 60 240 480 65 250 500 70 260 520 75 270 550 80 280 580 85 290 600 90 300 620 95 310 650 100 320 110 330 See the table below for the corresponding values Output signal limit Over range Fault 2 5 Faul...

Page 6: ...and Full scale values RTD Connection 2 wires 3 wires or 4 wires 50 60 Hz Rejection Absent or Present Measurement filter Absent or Present 1 2 5 10 30 60 seconds Output Normal 4 20 mA o Reversed 20 4 m...

Page 7: ...he resistance of the connection cables In order for compensation to be correct it is necessary that the resistance values of each conductors be the same because in order to perform compensation the in...

Page 8: ...to dispose of it Instead it should be handed over to an applicable collection point for the recycling of electrical and electronic equipment By ensuring this product is disposed of correctly you will...

Reviews: