MI00096 -E

3

ENGLISH - 7/8

Input

The module accepts a current or voltage input signal.

The use of shield cables is recommended for the electronic connections.

Voltage input

Terminal 1: Voltage input up to 30 VDC (current carrying capacity 0 - 15 VDC and 0 -
30 VDC).
Terminal 2: Voltage input up to 10 V.
Terminal 4: Return

Current input

Terminal 3: Current input.
Terminal 4: Return

Output

Voltage connection - Current connection (applied current)

The use of shield cables is recommended for the electronic connections.

1

5

6

7

8

2

3

4

POWER
SUPPLY

OUTPUT

INPUT

V / I

+

-

1

5

6

7

8

2

3

4

POWER
SUPPLY

OUTPUT

INPUT

Voltage
max 30 Vdc

1

4

Voltage
max 10 Vdc

2

4

Current

3

4

V

V

+

+

mA

Note: in order to reduce the instrument's dissipation, we recommend either using the
output for voltage or guaranteeing a load of > 250

n

Ω

to the curre t output.

Summary of Contents for K109UI

Page 1: ...mm DIN driver power supply available by bus quick fit couplings by spring type terminals 3 point insulation onsite configuration by DIP switch Technical Features Power supply Consumption 19 2 30 Vdc M...

Page 2: ...of range limiter device triggered or input saturation Internal fault Spring terminals 0 2 2 5 mm 2 8 mm EN50081 2 electromagnetic emission industrial surroundings EN50082 2 electromagnetic immunity i...

Page 3: ...Y OUTPUT INPUT 19 2 30 Vdc P 500 mW V I Range 150 650 C Load R 500 R 2 k Test Voltage 1 5 kV 50 Hz 1 min Amb Temp 20 65 C m W W V I 1 Attach the module in the upper part of the rail 2 Press the module...

Page 4: ...esent No None 0 20 mA 5 limit SETTING OF THE DIP SWITCHES Factory setting Note for all following tables The indication indicates that the DIP switch is set in Position 1 ON No indication is provided w...

Page 5: ...5 25 Vdc 0 75 Vdc 1 5 Vdc 0 Vdc 0 20 mA 4 20 mA 20 0 mA 5 20 4 mA 5 0 10 Vdc 0 5 Vdc 1 5 Vdc 2 10 Vdc 5 These are inverse output ranges that are useful whenever the linearisation applied is incompatib...

Page 6: ...wer supply to the modules via bus connector in this way eliminating the need to connect power supply to each module The bus can be supplied from any of the modules the total absorption of the bus must...

Page 7: ...turn Current input Terminal 3 Current input Terminal 4 Return Output Voltage connection Current connection applied current The use of shield cables is recommended for the electronic connections 1 5 6...

Page 8: ...ct is disposed of correctly you will help prevent potential negative consequences to the environment and humanhealth whichcouldotherwisebecausedbyinappropriatedisposalofthisproduct Therecyclingof mate...

Reviews: