MI00096 -E
3
ENGLISH - 4/8
All the module DIP switches are at pos. 0 as defaut configuration.
This set correspond to the following configuration :
It is understood that this configuration is valid only with all the DIP switches at position 0.
If also one Dip is moved, it is necessary to set all the other parameter as indicated on
the following tables.
Input signal
50-60 Hz mains frequency rejection
Input filter
Inversion
Linearisation
Output signal
Input Out-of-range
0 - 20 mA
50 Hz
Present
No
None
0 - 20 mA
±
5% limit
SETTING OF THE DIP-SWITCHES
Factory setting
Note: for all following tables
The indication
indicates that the DIP-switch is set in Position 1 (ON).
No indication is provided when the DIP-switch is set in Position 0 (OFF).
INPUT SIGNAL
1
SW1
2 3
4 - 20 mA
2 - 10 Vdc
0 - 20 mA
0 - 10 Vdc
1 - 5 Vdc
0 - 5 Vdc
0 - 30 Vdc
0 - 15 Vdc
50-60 Hz MAINS FREQUENCY REJECTION
4
SW1
50 Hz
60 Hz
INPUT FILTER (*)
5
SW1
Absent
Present
INVERSION
6
SW1
Absent
Present
(*) The filter increases the rejection of the disturbance to the mains frequency, and
stabilizes the reading reducing the measure noise. It is advised to hold it always
inserted, but that the maximum speed of answer is not demanded.