K109UI

V - mA CONVERTER
WITH 3-POINT GALVANIC INSULATION

General Description

The K109UI instrument is a V - mA converter with 3-point galvanic insulation designed
for industrial standard voltage or current signals with passive input and active output.
Analogue/digital conversion takes place at 14 bit on every input range.
The instrument also provides the following functions:

Rejection programmable for 50 or 60 Hz mains frequency.

Additional reading stabilisation filter.

Inversion of the input and inverted output scales
Input Out-of-Range programmable to 2.5% or 5.0%
SQRT function.
Linearisation for horizontal cylindrical tanks.

The module is also characterised by its extremely compact size, coupling to 35 mm DIN
driver, power supply available by bus, quick fit couplings by spring-type terminals, 3-
point insulation, onsite configuration by DIP-switch.

Technical Features

Power supply :
Consumption :

19,2 - 30 Vdc
Max 22 mA at 24 Vdc  ( 20 mA output )

Voltage input (max. 50 V) :
Voltage input (max. 30 V) :

Current input (max. 24 V) :
Permissible max. Input Out-of-
Range :

0 - 15 V, 0 - 30 V, Input Impedance: 325 k

Ω

0 - 10 V, 2 - 10 V, 0 - 5 V, 1 - 5 V,
Input Impedance: 110 k

Ω

0 - 20 mA, 4 - 20 mA, Input Impedance: 35

Ω

± 2,5 or ± 5% depending on setting (see section on
Input Out-of-Range Limits)

Digital, 32 bit floating-point calculation
14 bit on every input range

Processing :
ADC :

0 - 5 Vdc, 1 - 5 Vdc, 0 - 10 Vdc and 10 - 0 Vdc
Minima load resistance:  2 K

Ω

0 - 20 mA, 4 - 20 mA, 20 - 0 mA e 20 - 4 mA
Maximum load resistance:  500

Ω

± 30 V
Fixed (see section on Output Out-of-Range Limits)

approximately 25 mA

Voltage output :

Current output :

Maximum applied Voltage :
Permissible max. Output Out-of-
Range:
Current output protection :

Summary of Contents for K109UI

Page 1: ...mm DIN driver power supply available by bus quick fit couplings by spring type terminals 3 point insulation onsite configuration by DIP switch Technical Features Power supply Consumption 19 2 30 Vdc M...

Page 2: ...of range limiter device triggered or input saturation Internal fault Spring terminals 0 2 2 5 mm 2 8 mm EN50081 2 electromagnetic emission industrial surroundings EN50082 2 electromagnetic immunity i...

Page 3: ...Y OUTPUT INPUT 19 2 30 Vdc P 500 mW V I Range 150 650 C Load R 500 R 2 k Test Voltage 1 5 kV 50 Hz 1 min Amb Temp 20 65 C m W W V I 1 Attach the module in the upper part of the rail 2 Press the module...

Page 4: ...esent No None 0 20 mA 5 limit SETTING OF THE DIP SWITCHES Factory setting Note for all following tables The indication indicates that the DIP switch is set in Position 1 ON No indication is provided w...

Page 5: ...5 25 Vdc 0 75 Vdc 1 5 Vdc 0 Vdc 0 20 mA 4 20 mA 20 0 mA 5 20 4 mA 5 0 10 Vdc 0 5 Vdc 1 5 Vdc 2 10 Vdc 5 These are inverse output ranges that are useful whenever the linearisation applied is incompatib...

Page 6: ...wer supply to the modules via bus connector in this way eliminating the need to connect power supply to each module The bus can be supplied from any of the modules the total absorption of the bus must...

Page 7: ...turn Current input Terminal 3 Current input Terminal 4 Return Output Voltage connection Current connection applied current The use of shield cables is recommended for the electronic connections 1 5 6...

Page 8: ...ct is disposed of correctly you will help prevent potential negative consequences to the environment and humanhealth whichcouldotherwisebecausedbyinappropriatedisposalofthisproduct Therecyclingof mate...

Reviews: