PRODUCT INSTRUCTION
ATS system is designed for mains power supply off and starts generator for emergency power supply on. When
mains power supply off,the generator will start in 2-6 seconds,and then supplys power to load.When mains power
supply on,the ATS system will automatically transfer switch to main power supply,and then stop the generator in 2-6
seconds. 1.1 This system use SCM core and digital technics to control and manager automatic working system. 1.2
Easy installation and operation 1.3 Automatic working without people inspection.When transfer broken the system
will remain error record,and indicate engineer to inspect and resetup.Don’t worry about mains power supply and
generator power supply action same time. 1.4 There is a battery charger inside,and charge the battery of generator
aitomaticlally.
OPERATION STEPS
Use the cable to connect the ATS box to the generator control panel,and switch the electric door lock to “OFF”
position.(Only for diesel generator,for gasoline generator please switch to “ON”position) 2.1 Automatic postion setup
Press AUTO button, the indicator light AUTO will be on, ATS system works automaticly. 2.2 ATS system working When
the ATS system works automatically, if mains power supply off,ATS system will automatically open air damper control
and start the generator in 2 seconds,and wait the generator run 5 seconds,system will switch load to generator
power supply. 2.3 ATS system start 3 times When generator can not start well,ATS system will start generator
circularly 3 times as below Mains power supply off
generator start 3 seconds first time
start unsuccessfully and wait
5 seconds
generator start 4 seconds second time
start unsuccessfully and wait 5 seconds
generator start 5 seconds
third time NOTICE:When generator can not start successfully in 3 times,the indicator light "FAULT" will be on. 2.4
Generator stop When mains power supply on again,ATS system will transfer load to mains power
supply,and generator will stop after running 5 seconds without load. 2.5 Manual start If you don't need ATS system to
work automatically,please put the switch to "MANUAL" position. 2.6 Automatic air damper control If generator have
air damper control,when generator start,ATS system will automatically open it and close it after generator start
successfully.
Battery maintenancei
ATS system will charge the battery automatically,the charge current is 2A.
Summary of Contents for SC13000ATS
Page 3: ...Italia Star Com Due S R L www italiastar ro info italiastar ro 004 021 433 03 27 3...
Page 41: ...Italia Star Com Due S R L www italiastar ro info italiastar ro 004 021 433 03 27 41...
Page 49: ...Italia Star Com Due S R L www italiastar ro info italiastar ro 004 021 433 03 27 ATS 49...
Page 50: ...Italia Star Com Due S R L www italiastar ro info italiastar ro 004 021 433 03 27 50...
Page 74: ...Italia Star Com Due S R L www italiastar ro info italiastar ro 004 021 433 03 27 74...