3. Installation guidelines
When unpacking, check the Breaktank for damage, visible defects, etc. caused by transport. Contact
SEM Water Treatment within 4 working days.
3.1 Hydronic installation
•
Place the Breaktank on a flat surface or use the optional wall mounting bracket. Preferably in
the vicinity of a wall socket (230V), a cold water faucet and a sewer connection.
•
It is recommended to provide the water supply with a shut-off valve and 500u filter. The
connection size of the water supply is 1/2 "F.
•
The connection dimension on the discharge side of the break tank is 25 mm F Glue sleeve.
•
The rectangular overflow opening may not be closed.
•
The free outlet connection ¾ "F can be connected to a sewer with a 32 mm pipe.
•
The drain (drain) connection has a ½ "plug. This allows the tank to be emptied.
•
The installation example below gives a good idea of how the break tank can be connected to
the circulation system. Always ensure that fresh water is added to the filter, but after the
measuring point of the automation (W.H.V.B.Z requirement)
The overflow must always have a free range. The overflow may never be closed. The
breaktank will no longer function properly when the overflow is closed.