Output current
The STS 15 sensor is equipped with a 4…20
mA output to
return the turbidity values. The output current is
configured by means of the following parameters:
"AO min" sets the measuring range minimum and respectively the
4 mA point.
"AO max" sets the measuring range maximum and respectively
the 20 mA point.
"Damping"
sets the damping applied on display and output
current.
5.4
Switching point
The STS 15 sensor is equipped with a PNP switching
output that can be configured by means of four
parameters.
"DO On" sets the switch-on point and "DO Off" the switch-off
point.
Together, these two parameters define the function of the
switching output:
If "DO On" is lower than "DO Off", the output is switched on if the
measuring value is between the switching points (window
function).