If "DO On" is higher than "DO Off", the output is switched on if
"DO On" is exceeded by the measuring value. It is not switched
off before the "DO Off" measuring value is fallen below (hysteresis
function).
If "Do On" and "DO Off" are identical, the output is switched on if
the "DO On + DO Off" switching value is exceeded by the
measuring value and switched off if the "DO On + DO Off"
switching value is fallen below again.
In the range of 0 to 100 %, both parameters can be set
independently.
"Do funct" reverts the function of the switching output.
If the value is set to NO, the switching output acts as NO contact.
If the value is set to NC, the switching output acts as NC contact.
"DO delay" applies a delay of up to 200s to the reaction of the
switching output. This value applies for both, switching on and
switching off.
Summary of Contents for STS-15