CCM 164
–
User Manual
–
GB / UK
44
Output
#Qn (<txt>)
#Qn <level> <ON time>
Parameter
n = {1,2...4}
<txt>
<level>
<On time>
Output’s number.
Output’s name, maximum 16 characters.
Level is ON or OFF
On time in seconds, {1.2...3600}
Configure
#Q1 (Lamp 1)
#Q1 ON
#Q1 ON 60
OK: Q1 defined
OK: Q1 = ON
- Turns on Output Q1 invariably
OK: Q1 = ON 60sec
- Turns on Output Q1 for 60 seconds
Retrieve
#Q??
#Q1??
#Q1?
#Q1 ?
#Q?
#Q ?
#Qn (txt) #Qn <level> <ON time>
#Q1 (Lamp 1)
ON
Lamp 1 = ON
ON OFF OFF OFF
Q1 = ON Q2 = OFF Q3 = OFF Q4 = OFF
NB: The command is rejected if the output is being used in a rule.
Bit Register
#Bn (<txt>)
#Bn <level> <ON time>
Parameter
n = {1,2...4}
<txt>
<level>
<On time>
The bit register’s number.
The bit register’s name,
maximum 16 characters
Level is ON or OFF
On time in seconds, range {1..3600} seconds.
Configure
#B1 (Reaction1)
#B1 ON
#B1 ON 60
OK: B1 defined
OK: B1 = ON
- Turns on Output B1 invariably
OK: B1 = ON 60sec
- Turns on Output B1 for 60 seconds
Retrieve
#B??
#B1??
#B1?
#B1 ?
#B?
#B ?
#Bn (txt) #Bn <level> <ON time>
#B1 (Reaction1)
ON
Reaktion1 = ON
ON OFF OFF OFF …
B1 = ON B2 = OFF B3 = OFF B4 = OFF …
NB: The command is rejected if the bit register is being used in a rule.