Input and Output Definition
CCM164 has one 4-20 mA power input. For configuring different types of sensors with different
measuring ranges, use the following command:
#AIn (<txt>) R<resolution> U<unit> L<low> H<high>
n
is the power input’s number
Options: 1
<txt>
the name of the input
May not be empty
Maximum 16 characters
Refrain from using # [] () *
<resolution>
how many decimal numbers are used
Options:
1, 0.1, 0.01, 0.001
<unit>
Unit text up to 5 characters
E.g.
“Bar” for the unit of pressure
<low>
Low value at 4 mA
Options:
-
99999…99999
<high>
High value at 20 mA
Options:
-
99999…99999
Example:
Configure power input as a 0-10 m water level.
Typical errors:
NB: the text field may not be empty
CCM164 has 6 inputs, each of which can be configured to either analogue or digital. By default, all 6
inputs are digital. The following should be used to configure an analogue voltage input:
#In (<txt>) R<resolution> U<unit> L<low> H<high>
n
is the input’s number
Options: 1,2…6
<Txt>
the name of the input
May not be empty
Maximum 16 characters
Refrain from using # [] () *
<resolution>
how many decimal numbers are used
Options:
1, 0.1, 0.01, 0.001
<unit>
Unit text up to 5 characters
E.g. “Bar” for the unit of pressure
<low>
Low value at 0V
Options:
-
99999…99999
<high>
High value at 10V
Options:
-
99999…99999
Example:
Configure voltage input to 0-10 bars of pressure.
Example:
Configure voltage input at a -5m to 5m water level.
#AI1 (Waterlevel) R0.1 Um L0.0 H10.0
OK: AI1 defined
#AI1 R0.1 Um L0.0 H10.0
Error command unknown
:
#AI1 R0.1 Um L0.0 H10.0
#I1 (Pressure) R0.01 Ubar L0.00 H10.00
OK: I1 defined
#I2 (Waterlevel) R1 Um L-5 H5
OK: I2 defined