CCM 164
–
User Manual
–
GB / UK
20
Number of <action>
<act1> <act2> <act3> <act4>
<act1>, <act2>, <act3>, <act4>
Options:
Qn, Bn, P12...8, M12...8, !Qn, !Bn,
May be empty
Example:
When Digital Input 1 is high, Output 1, 2 and Bit 1 are set to high, the message “open” is sent
to tel.nos. P4 and P5.
Typical errors:
NB: Max 4 actions. Q and B can’t have more outputs like P and M can.
Options for Qn and Bn
=Qn
the value of <condition> becomes Qn
=!Qn
the opposite value of <condition> becomes
Qn
TQn
changes the Qn value once
QnDt
sets Qn to high for ‘t’ seconds
!QnDt
sets Qn to low for ‘t’ seconds
=Bn
the value of <condition> becomes Bn
=!Bn
the opposite value of <condition> becomes
Bn
TBn
changes the Bn value once
BnDt
sets Bn to high for ‘t’ seconds
!BnDt
sets Bn to low for ‘t’ seconds
Example:
When Voltage Input 1 is high, Output 1 is high. When Voltage Input 1 is low, Output 1 is low
NB: =Qn and =!Qn are the only actions that respond to a false <condition>
#A1 (Open) I1 Q1 Q2 B3 P45
OK: A1 defined
#A1 (Open) I1 Q1 B3 P45 Q2 !Q3
Error command unknown
:
#A1 (Open) I1 Q1 B3 P45 Q2 !Q3
#A1 (Open) I1 Q124 B3 P45
Error in command parameters: Q124
#A1 (on/off) I1 =Q1
OK: A1 defined
#Z1 1 1 1
OK: Z1 = 1 1 1