SP PRO SERIES SPECIFICATIONS
SPMC240
SPMC241
SPMC481
SPMC482
SPMC1201
SPLC1200
SPLC1202
Nominal batter voltage
24 V
24 V
48 V
48 V
120 V
120 V
120 V
Continuous, output power
Continuous, charge current
@ 25°C
3,000 W
125 A
4,500 W
188 A
5,000 W
104 A
7,500 W
156 A
7,500 W
63 A
15,000 W
125 A
20,000 W
167 A
Continuous grid export power
rated output
20 second load rating
20 second output current
@ 40°C
7,500 W
28 A
10,500 W
40 A
12,000 W
47 A
18,000 W
70 A
18,000 W
70 A
33,000 W
135 A
44,000 W
180 A
1 minute output power
@ 40°C
5,400 W
7,600 W
8,700 W
13,000 W
13,000 W
26,000 W
35,000 W
60 minute output power
@ 40°C
3,200 W
4,700 W
5,300 W
8,000 W
8,000 W
18,000 W
24,000 W
DC input voltage range
20 - 34 V
20 - 34 V
40 - 68 V
40 - 68 V
100 - 170 V
100 - 170 V
100 - 170 V
TRANSFER SWITCH (Synchronous)
AC transfer current capacity
63 A
125 A
125 A
Max AC input source, (generator/grid)
15 kVA
30 kVA
30 kVA
Max total output to Load, AC inverter
15 kVA
30 kVA
30 kVA
AC transfer time
no-break
If grid fails
0 - 0.03 seconds
Battery charger type
Temperature compensated, 5 stage, power factor corrected with dual stage float
EFFICIENCy
DC consumption idle
6 W
DC consumption standby (Econo Mode)
12 - 20 W
n/a
ON with no load
25 W
33 W
35 W
43 W
43 W
89 W
90 W
Peak efficiency – all modes
95%
95%
95.5%
96%
96.5%
97.2%
97.2%
10% load
90%
90.5%
91%
91%
91.5%
93.3%
94.8%
20% load
92.5%
93%
94%
94%
94%
95.8%
96.8%
50% load
94%
94.5%
95%
95.5%
96%
97.2%
97.1%
100% load
90%
91%
92.5%
93%
93.5%
96.8%
95.5%
AC OUTPUT (standalone)
Range
210 to 240 V +/- 0.5%
Regulation
<1% droop 0-100% rated load (<2% @ 150%, <5% @200%)
THD
<3% @ 0-200% rated load
Frequency
50 or 60 Hz +/-0.005% standalone
AC SOURCE (input)
Nominal voltage
240 V~
AC current (Recharge, Bypass & Normal
modes)
63 A
125 A
125 A
Tolerance on nominal voltage
Configurable 204 to 264 V~
Nominal input frequency
50/60 Hz
Tolerance on nominal frequency
Config/- 1% to 10%
Generator can be started by
Battery SoC, DC voltage, battery load, unit temperature, time & remote control
FEATURES
Battery temperature sensor
Included
Mid point battery voltage sensing
Included
Front panel display and controls
22 x LED indicators with auto adjusting intensity.
Display indicates, charger status, remaining usable battery capacity, alarms, AC status.
AC status indicators powered from AC voltage.
Generator control button. On button. Silence Alarm button.
Digital Inputs
4 of: Max 60 V DC ( Active > +10 V, Inactive < +3 V )
Shunt Inputs
2 of: +/-75 mV, adjustable 25 A to 500 A
Analogue Inputs
2 general purpose logged 0-60 V
n/a
Relay Outputs
4 of: 60 V, 500 mA
Digital outputs
3 of: 60 V, 5 mA
Communication ports
USB and RS232 (optional Wireless and Ethernet)
Memory retention of settings & data
Permanent
SP LINK configuration and monitoring software
Standard, allows configuration of parameters and monitoring of parameters and SP PRO display remotely.
Dimensions (mounted) W x H x D
375 x 690 x 220
540 x 870
x 293
540 x 870
x 293
Weight (with wall mount)
35 kg
39 kg
40 kg
42 kg
42 kg
113 kg
115 kg
Standards
IEC 62040-1-1:2002 / AS 62040.1.1-2003 with CB certificate
AS/NZS 61000-6-3 2007
AS/NZS 61000-6-4 2007
Grid Protection
AS 4777.2 2005 and AS 4777.3 2005
Protection
IP43