SERVICE | Troubleshooting
Doc #OI0003 Part #004122 Rev19 2014
|
67
1.
Alarm Silence button
- When the SP PRO detects an alert condition within the power it will sound its
internal audible alarm. Pressing this button will silence the alarm for this instance only. Alarm will resound
with a new alert condition
2.
Alarms
OVERTEMP
Yellow SP PRO is approaching an over temperature condition due to high loads, high ambient
temperatures or obstructed cooling air flow.
Red
SP PRO has shutdown due to an over temperature condition caused by high loads, high
ambient temperatures or obstructed cooling air flow.
Solution
1. Reduce the load on the system
2. Check and clear fan or fan filter. See “Cleaning the Fan and Fan filter” on page 64
SHUTDOWN
Yellow
SP PRO is approaching a shutdown condition
Red
SP PRO has shutdown
Solution
See next section “Troubleshooting with SP LINK” on page 68
ATTENTION
Off
Normal operation - System is operating normally
Yellow
Attention Required, Fan Service Request. See “Cleaning the Fan and Fan filter” on
page 64
Flashing Yellow Either Clean Fan, Fan Fault or Capacitor Bank
Red
Immediate Attention required.
Flashing RED
Unit Fault.
Solution
See next section “Troubleshooting with SP LINK” on page 68
3.
Battery Indicator
Top LED Flashing RED Instant Hi DC Voltage Shutdown. Battery or battery wiring fault
Bottom LED Yellow
Low Battery. Battery needs charging
Bottom LED Red
Low Battery Shutdown. Inverter has shut down due to flat of faulty battery
Bottom LED Flash RED Instant Low DC Voltage Shutdown. Battery or battery wiring fault.
Solution
1. Give battery bank a full charge and equalise charge.
2. Check all battery wiring including the battery bank interconnections, connections at the DC fuse or
CB and the main battery connection to the SP PRO.
3. Check all battery sense/pro-charge wiring.
4. Check for faulty or failed cells withing the battery bank.
NOTE
: When all LEDs are flashing RED the inverter has been put in Low DC Shutdown Override by the
user. In emergency situations, this override enables the SP PRO to be forced to work beyond the battery
shutdown limits. The SP PRO will continue to operate at reduced capacity until the battery can no longer
supply enough power to keep the inverter and loads running. Please remember that this feature should
only be used in an emergency as it overrides the SP PRO normal battery shutdown protections and may
damage the batteries or connected equipment.
4.
Generator
Flashing Yellow Generator is not available for auto start. The “Generator Available signal” is not active.
See next section “Troubleshooting with SP LINK” on page 68
Flashing Red
There is a generator fault
Solution
1. Check the Generator Available signal.
2. Check the generator and clear the fault
3. Try and start the generator manually.