Installation | Interface Port RS485
Doc. No. 982056, Version 01, SelectSun 40K
|
31
Portal
Data Logger /
Park Control
Ethernet
RS485+ RS485- Ref.
4
4
3
3
2 2
4
4
3
3
2
4
Bus
termination
1
3 2
2
4
3
2
Inverter
1
Inverter
2
Inverter n
Fig. 12: Standard interface
When using this interface, please note that each device using the bus requires a unique address.
The bus termination is made by means of wire jumpers on RS485 OUT to the last bus user (inverter “n”).
Pin
Signal
Pin 1
(only used for termination)
Pin 2
RS485 +
Pin 3
RS485 -
Pin 4
Reference
Fig. 13: Connector M12 x 1 straight, shielded; pole arrangement:male M12, 4 pins, A-coded, view of male connector side
NOTICE
In order to ensure IP 65 protection and the required and declared conformity with the
domestic EMC standard a PHOENIX CONTACT type M12MS SACC-4SC SH plug
and a shielded cable must be used. The outer diameter of the connecting cable can
be max. 8 mm.
Failure to observe this can lead to damage to the inverter and therefore void the
warranty.