Installation | Ethernet Interface Connection
32 | Doc. No. 982056, Version 01, SelectSun 40K
NOTICE
Component damage and communication malfunctions
Reversing the RS485 connecting cables and sensor cables results in defects and
malfunctions. If inverters are connected in series, a reversed RS485 can damage
further connected inverters.
Make sure that each of the RS485 connection plugs is connected with the
RS485 receptacle intended for it.
If the connectors are reversed, correctly plug the RS485 connecting cables
immediately.
4.15 Ethernet Interface Connection
The Ethernet interface supports Modbus TCP/IP protocol, and is Sunspec compliant, which can be used for
transmission of data, for example, to a data logger of a remote monitoring system. Daisy-chaining of devices
is not supported. Each inverter must be connected to an ethernet switch, in parallel.
Please use an Ethernet cable with S/FTP design (shielded foiled twisted pair) and Phoenix Contact plug type
Quickon VS-08-RJ45-5-Q/IP67.