Configuration | Portal Monitoring
Doc. No. 982056, Version 01, SelectSun 40K
|
45
This address is required for communicating with the inverter via RS485.
After entering the address, restart the inverter to activate the new address.
Protocol type:
1: USS protocol (preset)
2: (not used)
3: Meteocontrol USS
4: Modbus RTU Sunspec
(address 0 cannot be used – address 0 is automatically set to address 1!)
5: Multimode USS / Modbus RTU Sunspec
(in Multimode, you cannot use USS address 0 and 2!)
Baud rate:
57600 (preset and recommended)
115200 (for short RS485 networks)
Parity:
even
Handshake:
no
Data bits:
8
Stop bits:
1
Protocol:
USS protocol
6.7
Portal Monitoring
To ensure the inverter sends data via Ethernet to the monitoring portal, the portal monitoring must be active.
Open Menu Configuration > Portal Monitoring and enter the following value:
0 = Portal monitoring via Ethernet not active
1 = Portal monitoring via Ethernet active
6.8
Sending Config
Menu Configuration > Portal monitoring > Config sending
Notice
If the inverter is connected with RS485 to the∙control device, the setting 0
(Portal Monitoring via Ethernet not active) must be used!