TB XRW1-4 04.01 E
9
3.2.5
Parameter settings
Setting parameters
Unit
Range
∆
/Y
input transformer connection
Y = star
DELT = Delta
U1<
Pick-up value for the 1
st
undervoltage step
V
4 - 800
tU1<
Tripping time for the 1
st
undervoltage step
s
0.2 - 1500
tU1< back Reverse run of the 1
st
tripping time is active
YES/NO
U2<
Pick-up value for the 2
nd
undervoltage step
V
4 - 800
tU2<
Tripping time for the 2
nd
undervoltage step
s
0.2 - 1500
tU2< back Reverse run of the 2
nd
tripping time is active
YES/NO
U3<
Pick-up value for the 3
rd
undervoltage step
V
4 - 800
tU3<
Tripping time for the 3
rd
undervoltage step
s
0.04 - 300
tU3< back Reverse run of the 3
rd
tripping time is active
YES/NO
U4<
Pick-up value for the 4
th
undervoltage step
V
4 - 800
tU4<
Tripping time for the 4
th
undervoltage step
s
0.04 - 300
tU4< back Reverse run of the 4
th
tripping time is active
YES/NO
U1>
Pick-up value for the 1
st
overvoltage step
V
4 - 800
tU1>
Tripping time for the 1
st
overvoltage step
s
0.2 - 1500
tU1> back Reverse run of the 1
st
tripping time is active
YES/NO
U2>
Pick-up value for the 2
nd
overvoltage step
V
4 - 800
tU2>
Tripping time for the 2
nd
overvoltage step
s
0.2 - 1500
tU2> back Reverse run of the 2
nd
tripping time is active
YES/NO
U3>
Pick-up value for the 3
rd
overvoltage step
V
4 - 800
tU3>
Tripping time for the 3
rd
overvoltage step
s
0.04 - 300
tU3> back Reverse run of the 3
rd
tripping time is active
YES/NO
U4>
Pick-up value for the 4
th
overvoltage step
V
4 - 800
tU4>
Tripping time for the 4
th
overvoltage step
s
0.04 - 300
tU4> back Reverse run of the 4
th
tripping time is active
YES/NO
f
N
rated frequency
Hz
50/60
T
frequency measuring repetition in periods
periods
2 - 99
f
1
pickup value for frequency element 1
Hz
30 - 70 or
40 - 80
t
f1
tripping delay for frequency element 1
s
t
fmin.
-50
f
2
pickup value for frequency element 2
Hz
30 - 70 or
40 - 80
t
f2
tripping delay for frequency element 2
s
t
fmin
-50
f
3
pickup value for frequency element 3
Hz
30 - 70 or
40 - 80
t
f3
tripping delay for frequency element 3
s
t
fmin
-50
df
pickup value for rate of frequency (dt/dt) in
Hz/s
0.2 - 10
dt
measuring repetition for df/dt
periods
2 - 64
U
B
<
voltage threshold value for frequency and df/dt element
V
20 - 400
LED blinking after excitation
NOFL/FLSH
RS
Slave address of the serial interface
1 - 32
Table 3.2: Sequence of parameter setting