5

 

MAGIQTOUCH/MAGIQCOOL 

COMPATIBLE EVAPORATIVE 

COOLERS

The previous Breezair and Braemar range 

has been replaced with MagIQtouch and 

MagIQcool compatible models.

Introduction of the MagIQtouch controller 

brings the following changes:

COMMUNICATION CABLE

•  Cable type

  

 

 

26AWG 7/0.16, 6 core flat communication cable 

with 6P/6C RJ12 plug connections (not backwards 

compatible with previous models) 

•  Cable lengths

  

 

 

Maximum recommended cable lengths changed 

due to increased power requirements of the 

MagIQtouch controller. Maximum cable length from 

controller to first cooler is 25m. (Each cooler is 

supplied with a 20m cable ex factory).

COMMISSIONING

•  Installation Wizard 

The introduction of a step by step Installation 

Wizard displayed on the MagIQtouch controller 

to assist with commissioning. (

NOTE:

 Installation 

Wizard is only available with MagIQtouch 

controllers).

FAULT MANAGEMENT

•  Fault display

  

 

 

Displayed with full explanation and service contact 

details.

•  Fault resolution 

  

 

Service menu assists with diagnosing faults, 

troubleshooting instructions, and retrieving 

component information.

•  Component testing 

Service Operating Screen provides full control of 

all water management components on a single 

screen, making testing easier.

•  Removing/Replacing MagIQtouch products

  

Automatic detection & step by step on screen 

instructions.

USER OPERATION

•  Clearer, more intuitive touch screen interface for 

easy operation

•  New operation features (e.g. 7 day program)

ILL1672-A

ILL1674-B

ILL1674-B

ILL1674-B

ILL1673-A

ILL1456-B

Previous 

Model

New Model

Default Wall  

Control

EXH

EXQ, EXS

MagIQtouch

EZH

EZQ

MagIQtouch

LCB

LCQ, LCS

MagIQtouch

CPL

CPQ

MagIQcool

BM

BMQ

MagIQcool

ILL1674-B

The MagIQcool controller has all the features 

of older wall controls, but can connect to 

RJ12 controls used in MagIQtouch coolers. 

It is offered as an entry level controller for 

evaporative cooler installations.

ILL1456-B

Summary of Contents for MagIQtouch

Page 1: ...SERVICE GUIDE MagIQtouch MagIQcool Controller compatible Breezair Braemar Coolair models 2015 2016 Original English Instructions ...

Page 2: ...WITCH 9 UNDERSTANDING THE MAGIQTOUCH SYSTEM 10 COMPONENT ADDRESSES 10 BEFORE POWER UP 10 SYSTEM DIAGRAMS 11 SINGLE EVAPORATIVE COOLER 11 GAS DUCTED HEATER OPTIONAL ADD ON COOLER 11 MULTIPLE EVAPORATIVE COOLERS 12 INSTALLATION OPTIONS 14 DEFAULT SINGLE COMPONENT 14 MULTIPLE COMPONENTS 14 INSTALLATION WIZARD 14 PHASE 1 SYSTEM DEFINITION 14 PHASE 2 INSTALLATION 14 CONTROLLER OR SYSTEM RESET 15 SETTIN...

Page 3: ...OF DRAIN VALVE WITH SHORTING PLUG 24 DIAGNOSTIC FAULT CODES 25 LED 1 HALL EFFECT SENSORS 25 LED 2 MOTOR THERMAL OVERLOAD 25 LED 3 FAN SPEED 26 LED 4 MAINS POWER 26 DIAGNOSTIC LED 27 SALINITY LED 27 FAN MOTOR TESTING 28 FAN MOTOR REMOVAL 28 FOR EXQ130 EXS140 COOLERS ONLY 29 REFITTING THE PAD FRAMES EXQ EXS EZQ 32 BRAEMAR LCQ LCS BMQ COOLAIR CPQ EVAPORATIVE COOLER 33 QUICK REFERENCE GUIDE 33 DIAGNOS...

Page 4: ...TALLATION TIPS 45 A12 14 BREEZAIR EXS PAD CONFIGURATION 46 ICON CONTROL BOX FAN SPEED LED BEHAVIOUR 47 A02 09 CIRCUIT PROTECTION FOR ICON 48 A13 08 ICON ELECTRICAL SUPPLY REQUIREMENTS 49 A16 08 WATER DISTRIBUTION HOSE CONNECTIONS 50 A06 07 FEAC WATER SUPPLY REQUIREMENTS 51 NOTES 52 MAGIQTOUCH SYSTEM TROUBLESHOOTING GUIDE 53 FREQUENTLY ASKED QUESTIONS 55 MAGIQTOUCH CONTROLLER 55 EVAPORATIVE COOLER ...

Page 5: ...vailable with MagIQtouch controllers FAULT MANAGEMENT Fault display Displayed with full explanation and service contact details Fault resolution Service menu assists with diagnosing faults troubleshooting instructions and retrieving component information Component testing Service Operating Screen provides full control of all water management components on a single screen making testing easier Remo...

Page 6: ...of the temperature sensing thermostat inside the controller The following points must be taken into consideration Avoid direct sunlight exposure Avoid mounting on external walls Avoid mounting the wall control near heat sources such as stoves and televisions Do not locate in the direct airflow of the duct outlets Do not locate in strong drafts or in dead spots such as cupboards drawers Always seal...

Page 7: ...c The installer can set up the MagIQtouch controller to take temperature and humidity readings from this external sensor and run the cooler accordingly Details of the MagIQtouch Air Sensor kit are as follows 094328 MagIQtouch Air Sensor MOUNTING LOCATION The Air Sensor will be used instead of the MagIQtouch controller for temperature sensing Follow the mounting location instructions in the MagIQto...

Page 8: ...ouch Link Module is a small T junction electronics board mounted in its own waterproof enclosure which is used to connect multiple MagIQtouch products together 094274 MagIQtouch Link Module in Enclosure Contents Qty Description 1 MaglQtouch Link Module in Enclosure 1 Communication Cable 3m 1 Literature ILL1790A No Link Module is required for a simple 1 cooler 1 controller installation However Link...

Page 9: ...s connection priorities 3 AIR SENSOR 2 HEATER OR OR 1 WALL CONTROL MAGIQTOUCH CONTROLLER 2 PREVIOUS JUNCTION PREVIOUS LINK MODULE 2 AIR SENSOR 1 GAS HEATER 3 NEXT JUNCTION NEXT LINK MODULE 1 EVAPORATIVE COOLER ILL1754 B ILL1829 A SETTING DIPSWITCH After connecting the cables ensure the dipswitch is set correctly The following table indicates how the dipswitch should be set depending on what produc...

Page 10: ...ide a T junction to connect MagIQtouch components into the main communication line The controller communicates through and not directly to the link module and therefore is not given an address BEFORE POWER UP To ensure the MagIQtouch component addressing process is completed correctly the following must be done before power up of the controller If there are no more than 1 of each component type e ...

Page 11: ...NSOR LINK MODULE ILL1758 B ILL1865 A Major Appliances Appliance Included With Appliance Qty Evaporative Cooler MagIQtouch Controller 20m Cable 1 Major Appliances Appliance Included With Appliance Qty Evaporative Cooler MagIQtouch Controller 20m Cable 1 Additional Kits Required P N Description Cable Inc Qty 094328 MagIQtouch Air Sensor 20m 1 094274 MagIQtouch Link Module in Enclosure 3m 1 ...

Page 12: ...E EVAPORATIVE COOLERS ILL1759 C Additional Kits Required P N Description Cable Inc Qty 094274 MagIQtouch Link Module in Enclosure 3m 1 x Cooler Major Appliances Appliance Included With Appliance Qty Evaporative Cooler MagIQtouch Controller 20m Cable 1 x Cooler ...

Page 13: ...RATIVE COOLERS ILL1867 B Major Appliances Appliance Included With Appliance Qty Evaporative Cooler MagIQtouch Controller 20m Cable 1 100 Additional Kits Required P N Description Cable Inc Qty 094328 MagIQtouch Air Sensor 20m 1 094274 MagIQtouch Link Module in Enclosure 3m 1 ...

Page 14: ...SE 1 SYSTEM DEFINITION For multiple component systems the installation wizard begins with a System Definition phase The installer must define exactly what components will be installed The screens that follow will depend on what has been defined PHASE 2 INSTALLATION Do not worry about memorising a particular sequence of screens for this process The steps and screens the controller moves through may...

Page 15: ...go through the System Installation Wizard again from the start ILL1596 B ILL1632 A It is possible to reset the whole system including all connected components or the controller only Use a pin or paperclip to press and hold the reset button located at the back of the controller This will cause the following screens to appear Some settings are protected by an access code to prevent customers changin...

Page 16: ...ss Adjust screen brightness when controller goes into sleep mode Status information Display For troubleshooting diagnostics Air Sensor Selection when Air Sensor is fitted Select Air Sensor to overdrive sensor in wall controller Software Revision Display MagIQtouch controller software revision Software revision 21R0415 and higher are compatible with TQ heaters and Invertair Add on coolers Simple Mo...

Page 17: ...control external to electronics eg continuous bleed No Water Thermostatic allows Thermostatic control in VENT mode No water present Cooling performance is limited Weather Seal Open Speed The cooler fan will turn on at the specified weather seal opening speed for the first 10 seconds each time it starts up It will then return to the set fan speed Prewet When COOL mode is activated the pump will run...

Page 18: ...nt to shut down and requires a service agent to resolve ILL1627 A Once the pin code is entered you will have access to component specific information This information includes About Appliance Fault Log Running History Last Known Operating Condition Service Operating Screen SERVICE OPERATING SCREEN The Service Operating Screen for each component installed in the system This screen can be used as a ...

Page 19: ...drain valve ON or OFF MANAGING COMPONENTS ADDING COMPONENTS The controller keeps a list of all the MagIQtouch installed components and regularly checks that all components are responding To add a new component simply connect it to the system and power up The controller will detect that a new component has been added and lead you through the set up process Important It is important that new compone...

Page 20: ...g the correct pin code 7378 the controller will do a scan to find what is connected to the system The screen will then display a list of all components in the installation both functional and faulty ILL1821 A ILL1638 B ILL1822 A At this point disconnect the component to be removed and press the MODIFY button This should cause the MagIQtouch controller to display a warning message where the compone...

Page 21: ...ode or escape from an alteration without storing a change press button instead of button Remember once step 5 has been carried out new parameter change is permanent until again altered 7 If no buttons are pushed on wall control after 3 minutes screen will reset to OFF state Procedure to enter parameter mode must be re initiated Parameters No Description Value A1 Water salinity control method selec...

Page 22: ...er will display a summary list of what it has found If this configuration is accepted the controller will be ready to operate the system The controller will scan for one type of component at a time The operator can skip to the next scan once they see all components of a particular type have been found CHANGING FROM MAGIQTOUCH TO MAGIQCOOL CONTROLLER The operating systems are different between the ...

Page 23: ...s of the model selected Spare Parts Information To identify and order Seeley International spare parts for Breezair Braemar Coolair and Convair products online go to seeleyinternational com get support spare parts Seeley International Technical Support 1300 650 399 Seeley Spare Parts Distributors 1300 367 437 Authorised Service Agents 1300 650 644 For access to Technical Installation Serve Informa...

Reviews: