72
Appendix D - Reporting
11.0
Appendix D - Reporting
11.1 Ademco Contact-ID MR-3318 Series Event Codes
Table 24 Contact-ID Event Codes
Event Description
Event
Family
Qualifier
Code
Group #
Contact #
Phone Line #1 trouble detected
Trouble
New event
1 351
00
000
Phone Line #2 trouble detected
Trouble
New event
1 352
00
000
Phone Line #1 trouble restored
Trouble
Restore
3 351
00
000
Phone Line #2 trouble restored
Trouble
Restore
3 352
00
000
Failure to report to an Account
Trouble
New event
1 354
Acct #
Acct #
Report to an Account successful
Trouble
Restore
3 354
Acct #
Acct #
RS-485 Communication Trouble
Trouble
New event
1 350
00
485
Periodic (24 hr) Test Event (NORMAL)
Test
New event
1 602
00
000
Periodic (24 hr) Test Event (OFF
NORMAL)
Test
New event
1 608
00
000
Manually initiated dialer test
Test
New event
1 601
00
000
Zone Fire Alarm
Alarm
New event
1 110
00
NNN
Zone Fire Alarm restored
Alarm
Restore
3 110
00
NNN
Zone Trouble detected
Trouble
New event
1 300
00
NNN
Zone Trouble restored
Trouble
Restore
3 300
00
NNN
Zone Supervisory condition
Supervisory
New event
1 200
00
NNN
Zone Supervisory restored
Supervisory
Restore 3
200
00
NNN
Water flow
Alarm
New event
1 113
00
NNN
Water flow restored
Alarm
Restore
3 113
00
NNN
Indicating Zone Trouble
Trouble
New event
1 320
00
NNN
Indicating Zone Trouble restored
Trouble
Restore
3 320
00
NNN
General Alarm
Alarm
New event
1 140
00
NNN
General Alarm restored
Alarm
Restore
3 140
00
NNN
AC power lost
Trouble
New event
1 301
00
000
AC power restored
Trouble
Restore 3
301
00
000
Battery Low
Trouble
New event
1 302
00
000
Battery Low restored
Trouble
Restore
3 302
00
000
Ground Fault
Trouble
New event
1 310
00
000
Ground Fault restored
Trouble
Restore
3 310
00
000